No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
S2-13
(3212)
Sequence Timer 3 Day
Selection
Tmr 3 Day Sel
0: Timer Disabled
1: Daily
2: Mon - Fri
3: Sat - Sun
4: Monday
5: Tuesday
6: Wednesday
7: Thursday
8: Friday
9: Saturday
10: Sunday
Sets the days for which sequence timer 3 is active.
0: Timer disabled
1: Daily
2: Mon - Fri
3: Sat - Sun
4: Monday
5: Tuesday
6: Wednesday
7: Thursday
8: Friday
9: Saturday
10: Sunday
Default: 0
Range: 0 to 10
–
S2-14
(3213)
Sequence Timer 3
Selection
Tmr 3 Seq Sel
0: Digital out only
1: Run
2: Run - PI Disable
3: AllowAlternation
Sets the action that occurs when sequence timer 3 is active.
0: Digital output only
1: Run
2: Run - PI disable
3: Allow Alternation
Default: 0
Range: 0 to 3
S2-15
(3214)
Sequence Timer 3
Reference Source
Tmr 3 Ref Source
0: Opr (dx-0x/Qx-0x)
1: Opr (dx-0x/Qx-0x)
2: Opr (dx-0x/Qx-0x)
3: Opr (dx-0x/Qx-0x)
4: Terminals
5: Serial Com
6: Option PCB
7: Pulse Input
8: Set by b1-01
Selects the frequency reference source used for running the
drive when sequence timer 3 is active (only applicable when
S2-14 is set to 1 or 2).
0: Operator (d1-01/Q1-01)
1: Operator (d1-02/Q1-02)
2: Operator (d1-03/Q1-03)
3: Operator (d1-04/Q1-04)
4: Terminals
5: Serial communication
6: Option card
7: Pulse input
8: Set by b1-01
Default: 8
Range: 0 to 8
–
S2-16
(3215)
Sequence Timer 4 Start
Time
Tmr 4 Start Time
Sets the start time for timer 4.
Default:
12:00AM
Min.: 12:00AM
Max.: 11:59PM
–
S2-17
(3216)
Sequence Timer 4 Stop
Time
Tmr 4 Stop Time
Sets the stop time for timer 4. The value must be set greater than
or equal to S2-16.
Default:
12:00AM
Min.: 12:00AM
Max.: 11:59PM
–
S2-18
(3217)
Sequence Timer 4 Day
Selection
Tmr 4 Day Sel
0: Timer Disabled
1: Daily
2: Mon - Fri
3: Sat - Sun
4: Monday
5: Tuesday
6: Wednesday
7: Thursday
8: Friday
9: Saturday
10: Sunday
Sets the days for which sequence timer 4 is active.
0: Timer disabled
1: Daily
2: Mon - Fri
3: Sat - Sun
4: Monday
5: Tuesday
6: Wednesday
7: Thursday
8: Friday
9: Saturday
10: Sunday
Default: 0
Range: 0 to 10
–
S2-19
(3218)
Sequence Timer 4
Selection
Tmr 4 Seq Sel
0: Digital Out Only
1: Run
2: Run - PI Disable
3: AllowAlternation
Sets the action that occurs when sequence timer 4 is active.
0: Digital output only
1: Run
2: Run - PI disable
3: Allow Alternation
Default: 0
Range: 0 to 3
S2-20
(3219)
Sequence Timer 4
Reference Source
Tmr 4 Ref Source
0: Opr (dx-0x/Qx-0x)
1: Opr (dx-0x/Qx-0x)
2: Opr (dx-0x/Qx-0x)
3: Opr (dx-0x/Qx-0x)
4: Terminals
5: Serial Com
6: Option PCB
7: Pulse Input
8: Set by b1-01
Selects the frequency reference source used for running the
drive when sequence timer 4 is active (only applicable when
S2-19 is set to 1 or 2).
0: Operator (d1-01/Q1-01)
1: Operator (d1-02/Q1-02)
2: Operator (d1-03/Q1-03)
3: Operator (d1-04/Q1-04)
4: Terminals
5: Serial communication
6: Option card
7: Pulse input
8: Set by b1-01
Default: 8
Range: 0 to 8
–
B.14 S: Special Application
350