Status indication X12: DI
n
1L+
–
LED (green)
Supply voltage available for DI
n
.0 ... .7
–
LEDs (green)
I+0.0 ... I+0.7
I+1.0 ... I+1.7
Starting with ca. 15V the signal "1" at the input is recognized and the according
LED is activated
6.7.3 Parameterization
1.
Start the Siemens SIMATIC Manager with your project and open the hardware con-
figurator.
2.
Place a profile rail.
3.
Configure on slot 2 the Siemens CPU 313C (6ES7 313-5BF03-0AB0 V2.6).
4.
Open the dialog window "Properties" by a double click to the
Count
submodule of
the CPU.
5.
As soon as you select the operating mode "Frequency measurement" to the corre-
sponding channel, a dialog window for the frequency measurement is created and
displayed and filled with default parameters.
6.
Execute the wished parameterization.
7.
Store the project with
‘Station
è
Save and compile’
.
8.
Transfer the project to the CPU.
In the following the parameters are listed which may be used for frequency measurement
configuration during hardware configuration. Parameters, which are not listed here, are
ignored by the CPU.
n
General
Here the short description of the counter function may be found. At Comment infor-
mation about the module such as purpose may be entered.
n
Addresses
Here the start address of the counter function is set.
Parameter overview
VIPA System 300S
+
Deployment I/O periphery
Frequency measurement > Parameterization
HB140 | CPU-SC | 313-5BF23 | en | 19-01
130