Table 3-8 Pin Map for 16 Pin I/O Connector
PIN
INPUT/
OUTPUT
FUNCTION
DESCRIPTION/NOTES
1 - 6
Reserved
7
Input
Return for remote shutdown
24 VDC signal will shut down and keep inverter
in shutdown mode.
Opto-isolated means that the control (remote
shutdown) is electrically separated from the
device (inverter).
8
Input
Remote shutdown
(opto-isolated)
9 - 14
Reserved
15
Output
Return for 24 VDC
Requires operation of auxiliary power supply for
the inverter
16
Output
Source for 24 VDC, 0.5 ADC
for auxiliary devices
Table 3-9 Connection Specifications for 16 Pin I/O Connector
WIRE SIZE
28-16 AWG (0.08-1.5 MM2)
TORQUE
5 in-lbs. (0.56 N-m)
TORQUE SCREWDRIVER SIZE
5/64 in. (2 mm)
Weather Station Connection (Optional)
Only use weather stations that connect using Ethernet. As with all other non-inverter Ethernet devices, these should be
connected outside of the Cluster LANs.
Resealing the Wiring Box
WARNING
Condensation and Water Ingress Will Cause Damage: The Solectria XGI™ inverter has a NEMA Type 4X enclosure. If
not properly installed all Type 4X enclosures are susceptible to water ingress and condensation that will damage