Electrical Installation AC, Method
DANGER
Electric Shock Hazard: Components with hazardous voltage and energy will electrocute operator. Operator shall avoid
touching live components with hazardous voltage and energy. Verify the absence of voltage using an appropriately
rated multimeter.
Always Wear Proper PPE: The proper Personal Protective Equipment (PPE) must be worn while working in close
proximity of hazardous voltage and energy.
Conduit Installation: All conduit connections must be made in such a way as to maintain the NEMA Type 4 rateing of
the enclosure. Failure to maintain the NEMA rating will void the warranty.
Table 3-4 Electrical Installation AC, Tools Required
TOOL
DESCRIPTION
SLOTTED SCREW DRIVER
3/16” or 4.75mm slotted screw driver
#3 PHILLIPS-HEAD TORQUE DRIVER
#3 Phillips-head torque driver, capable of 30 in/lbs
#2 PHILLIPS-HEAD TORQUE DRIVER
#2 Phillips-head torque driver, capable of 10 in/lbs
MULTIMETER
1000VDC/480VAC CAT III Multimeter
Figure 3-14 shows the locations for all AC and DC terminations in the Wire Box.
Figure 3-14 Wiring Box Connections (Independent Mode configuration shown)
Turn the AC and DC Switch OFF before opening the Wire Box.