A1-3
PARA-
SETTING RANGE
SETTING
FACTORY
USER
PARA.
METER
NAME
(AND UNITS)
INCREMENT
SETTING
SETTING
REF.
9:
Multi-step speed ref. cmd. D
n053
Multi-function Input
10: JOG Selection
1
5
Selection 4 (Terminal S4)
11: Accel/Decel time change cmd.
(5)
12: External Base Block (N.O.)
n054
Multi-function Input
13: External Base Block (N.C.)
1
6
Selection 5 (Terminal S5)
14: Speed search from max. freq.
(6)
Multi-function Input
15: Speed search from set freq.
n055
Selection 6 (Terminal S6)
16: Accel/Decel hold command
1
7
17: Remote/Local selection
(7)
18: Serial Communication / control ckt.
selection
19: Fast Stop - Fault (N.O.)
5.18
20: Fast Stop - Alarm (N.O.)
n056
Multi-function Input
21: Fast Stop - Fault (N.C.)
1
10
Selection 7 (Terminal S7)
22: Fast Stop - Alarm (N.C.)
(10)
23: PID control off
24: I value reset (PID)
25: I value hold (PID)
26: Over Heat Pre-alarm OH3
27: Accel/Decel Time Select 2
34: Up
0:
Fault
Multi-Function Output
1:
During running
n057
Selection 1
2:
Speed Agree
1
0
(Terminals MA, MB & MC)
3:
Zero Speed
4:
Frequency detection 1
5:
Frequency detection 2
6:
Overtorque detection (N.O.)
7:
Overtorque detection (N.C.)
8:
Undertorque Detection (N.O.)
Multi-Function Output
9:
Undertorque Detection (N.C.)
1
1
n058
Selection 2
10: Minor Fault
5.19
(Terminals P1 & PC)
11: During Base Block
12: Local / Remote
13: Ready
14: During auto restart
Multi-Function Output
15: During undervoltage
n059
Selection 3
16: During reverse run
(Terminals P2 & PC)
17: During speed search 1
2
18: Serial Comm. Controlled
19: PID feedback loss
20: Frequency Reference Loss Detect (N.O.)
``
21: Overheat Pre-alarm OH3 (N.O.)
n060
Analog Frequency Reference
0 to 255
1 (%)
100
Gain (term. FR to FC) (Note 4)
5.8
n061
Analog Frequency Reference
-100 to 100
1 (%)
0
Bias (term. FR to FC) (Note 4)
n062
Analog frequency reference
filter time constant
0.00 to 2.00
0.01 (sec)
0.10
(term. FR to FC) (Note 4)
n064
Frequency Reference Loss
0:
No Detection
1
0
5.33
Detection
1:
Continue to run at 80% of max. frequency
n065
Monitor Output0:
Analog monitor output
1
0
5.17
Selection
1:
Pulse monitor output
0:
Output frequency (10V = 100% Fmax)
1:
Output Current (10V = 100% drive
rated current)
2:
DC Bus Voltage
n066
Multi-function Analog Output
(10V = 400 VDC [800 VDC])
(Terminals AM & AC)
3:
Motor Torque
1
0
5.17
(10V = Motor rated torque)
4:
Output Power
(10V = Drive Capacity kW)
5:
Output Voltage 10V = n012 (voltage max)
6:
Frequency Reference
n067
Analog Monitor Gain (Note 4)
0.00 to 2.00
0.01
1.00
n068
Analog Frequency Reference
-255 to 255
1%
100
Gain (CN2, Voltage Ref Input)
n069
Analog Frequency Reference
-100 to 100
1%
0
5.32
Bias (CN2, Voltage Ref Input)
Table A1-1. Drive Parameters - Continued
Summary of Contents for SI-T/ V7
Page 1: ...V7 and V74X Drives Technical Manual Models MV and CIMR V7 Document Number TM V7 01...
Page 16: ...xiv Intentionally Left Blank...
Page 18: ...xvi...
Page 22: ...1 4 Continued 1 3 PHYSICAL INSTALLATION Figure 1 1b Component Identification...
Page 31: ...1 13 Continued 1 4 ELECTRICAL INSTALLATION Figure 1 4 Installation of Line Filter and V7 Drive...
Page 36: ...1 18...
Page 48: ...3 2...
Page 52: ...4 4...
Page 97: ...5 45 PID Block Diagram 5 28 PID CONTROL Continued...
Page 120: ...6 10...
Page 128: ...A1 8...
Page 132: ...A3 2...
Page 144: ...A6 6...
Page 148: ...A7 4...
Page 152: ...A8 4...
Page 156: ...I 4...