5-51
Continued
F.
Copy Function message list
Operator Description
Corrective
action
display
rdy
Drive is ready to perform a Copy Function
-
rEd
Read selected
Flashing: Read is being performed
-
Cpy
Writing (COPY) selected
Flashing: Write (Copy) is being performed
-
uFy
Verify selected
Flashing: Verify is being performed
-
uA
Drive capacity selected
-
Sno
Software number displayed
-
End
Read, Copy or Verify completed
-
PrE
Flashing: Attempt to execute Read while
Set Parameter n177 to a value of “1”
parameter Copy Access Selection (n177)
is set to " 0"
rdE
Flashing: Parameter could not be read
Confirm that the main circuit power supply
properly by the Read function, or, an
voltage is correct, then re-execute a Read
under voltage is detected during Read
CSE
Flashing A check sum error occurred in
The parameter data stored in the digital
the parameter data stored in the digital
operator is invalid and cannot be used.
operator
Re-execute Read to store the parameters in
the digital operator
dpS
Flashing: Parameter data in the drive
Check to see if the drives are the same type
and in the digital operator do not match.
(Ex.) Copying from a GPD 315/V7 and
writing to a GPD 305/J7
ndr
Flashing: No parameter data is stored
Execute a Read
in the digital operator
CPE
Flashing: Attempt to execute a Copy
Verify Voltage and Control Modes
or Verify between different voltage drives
or a different Control Mode
CyE
Flashing: An under voltage is detected
Confirm that the main circuit power supply
during a Copy execution
voltage is correct, then-execute a Copy
F04
A check sum error occurs in the
Initialize the constants. If an error occurs
parameter data stored in the inverter
again, replace the inverter due to a failure of
parameter memory element (EEPROM) in
the drive
uAE
Flashing: Attempt Execute Verify
Press the Data/Enter key to continue the
between different drive capacities
execution of Verify. Press stop to interrupt the
execution of Verify
.FE
Flashing: A communication error has
Check the connection between the drive and
occurred between the digital operator
the digital operator. If a communication error
and the drive
occurs be sure to re-execute Read or Copy
5.29 COPY FUNCTION
Summary of Contents for SI-T/ V7
Page 1: ...V7 and V74X Drives Technical Manual Models MV and CIMR V7 Document Number TM V7 01...
Page 16: ...xiv Intentionally Left Blank...
Page 18: ...xvi...
Page 22: ...1 4 Continued 1 3 PHYSICAL INSTALLATION Figure 1 1b Component Identification...
Page 31: ...1 13 Continued 1 4 ELECTRICAL INSTALLATION Figure 1 4 Installation of Line Filter and V7 Drive...
Page 36: ...1 18...
Page 48: ...3 2...
Page 52: ...4 4...
Page 97: ...5 45 PID Block Diagram 5 28 PID CONTROL Continued...
Page 120: ...6 10...
Page 128: ...A1 8...
Page 132: ...A3 2...
Page 144: ...A6 6...
Page 148: ...A7 4...
Page 152: ...A8 4...
Page 156: ...I 4...