VAN-V19001E [V1000→GA500]
29
/35
Parameter
No.
Name
V1000
GA500
Default
Your
customized
settings
Range
Default
Range
N6-01
Online
Tuning
Selection
1
0: Disabled
1 = Line-to-Line
Resistance Tuning
0
* When
replacing
V1000
with
GA500,
set N6-
01=1.
0: Disabled
1 = Line-to-Line
Resistance Tuning
2 = Voltage Correction
Tuning
* You cannot set N6-
01=2 if you have
enabled energy saving
mode (b8-01).
N8-51
Pull-in
Current @
Acceleration
(for PM)
50
0 to 200
50 for A1-
02=5, 80
for A1-
02=8
0 to 200 %
O1-03
Frequency
Display Unit
Selection
0
0 = In units of 0.01 Hz
1 = In units of 0.01%
(maximum output
frequency is 100%)
2 = In units of min
-1
(automatically calculated
based on the maximum
frequency and the number
of motor poles)
3 = User Units
0.5 for
A1-02=0
or 1, 0 for
other
0 = In units of 0.01 Hz
1 = In units of 0.01%
(maximum output
frequency is 100%)
2 = In units of min
-1
(automatically
calculated based on
the maximum
frequency and the
number of motor
poles)
3 = User Units
O1-05
LCD
brightness
adjustment
3
0 to 5
5
0 to 10