VAN-V19001E [V1000→GA500]
26
/35
5. Replacing the Parameters
5-1. Parameter Replacement Procedure
(1)
Prepare a list of your customized settings changed from the factory defaults.
If you can turn on the V1000, you are recommended to check the parameters changed from the factory defaults in
the V1000 Verify mode.
And take notes of your customized settings (changed values).
(2)
On the GA500, change the setting of A1-01 [Access Level Selection] from the factory default of 2 to 3 ([Expert
Level]).
(3)
If you use an induction motor (IM):
1) On the GA500, set A1-02 [Control Method Selection] to the same value as on the V1000.
2) On the GA500, set the E: motor parameter settings (changed values) to the same values on the V1000,
3) On the GA500, set the parameter settings other than the E: motor parameter settings (changed values) to the
same values as on the V1000 with reference to "5-3 Parameter Matching Table".
If you do not use an induction motor (IM):
On the GA500, set the parameter settings (changed values) to the same values as on the V1000 with reference to
"5-3 Parameter Matching Table".
5-2. Checking for Changed Parameters Using the V1000's Verify Mode
Turn on the V1000.
Open the Verify mode screen (with "vrFY" flashing) using the [Up arrow key] or [Down arrow key].
Push the [ENTER Key].
"nonE" appears if no parameters have been changed from the factory defaults.
If there are any changed parameters, they are displayed blinking.
Push the [ENTER Key] to view the settings (changed values).
Take notes of the displayed settings (changed values).
Push the [ESC] key. The parameters are displayed blinking again.
Push the [Up arrow key].
As long as there are changed parameters, they are displayed blinking one by one in the alphabetical order.
After the last changed parameter is displayed, the first displayed parameter is displayed again.
This procedure is complete when you have taken notes of all the changed parameters (values).
Turn off the V1000.
Note: Carefully note that the description above applies only to A1-02 [Control Method Selection] and that all other
parameters, including A1-
, A2-01 to A2-32, and E5-01 [PM Motor Code Selection], will not be displayed even
if they have been changed from the factory defaults.