V
I
A1 A2 A3
Jumper S1
Figure 3.34 Terminal A2 Set to Current Input; A1 and A3 Set to Voltage Input
Table 3.13 Jumper S1 Settings
Setting
Description
V (top position)
Voltage input (-10 to +10 V or 0 to 10 V)
I (bottom position)
Current input (4 to 20 mA or 0 to 20 mA)
Table 3.14 Voltage/Current Selection Parameter Details
No.
Parameter Name
Description
Setting
Range
Default
Setting
H3-01
Terminal A1 signal level selection
Selects the signal level for terminal A1.
0: 0 to 10 Vdc
1: 0 to 10 Vdc Bipolar
2: 4 to 20 mA
3: 0 to 20 mA
0 to 3
0
H3-05
Terminal A3 signal level selection
Selects the signal level for terminal A3.
0: 0 to 10 Vdc
1: 0 to 10 Vdc Bipolar
2: 4 to 20 mA
3: 0 to 20 mA
0 to 3
0
H3-09
Terminal A2 signal level selection
Selects the signal level for terminal A2.
0: 0 to 10 Vdc
1: 0 to 10 Vdc Bipolar
2: 4 to 20 mA
3: 0 to 20 mA
0 to 3
2
u
Terminal AM/FM Signal Selection
The signal type for terminals AM and FM can be set to either voltage or current output using jumper S5 on the terminal board
. When changing the setting of jumper S5, parameters H4-07 and H4-08 must be set accordingly.
The default selection is voltage output for both terminals.
Table 3.15 Jumper S5 Settings
Terminal
Voltage Output
Current Output
Terminal AM
AM
FM
V
I
AM
FM
V
I
Terminal FM
AM
FM
V
I
AM
FM
V
I
Table 3.16 Parameter H4-07 and H4-08 Details
No.
Parameter Name
Description
Setting
Range
Default
Setting
H4-07
Terminal AM signal level selection
0: 0 to 10 Vdc
1: -10 to 10 Vdc
2: 4 to 20 mA
0 to 2
0
H4-08
Terminal FM signal level selection
3.8 Control I/O Connections