u
U5: PID Monitors
No.
(Addr.
Hex)
Name
Description
Analog Output Level
Unit
U5-01
(57)
PID Feedback 1
Displays the PID feedback value.
10 V: 100%
U5-02
(63)
PID Input
Displays the amount of PID input (deviation between PID setpoint and
feedback).
10 V: 100%
0.01%
U5-03
(64)
PID Output
Displays PID control output.
10 V: 100%
0.01%
U5-04
(65)
PID Setpoint
Displays the PID setpoint.
10 V: 100%
U5-05
(7D2)
PID Differential Feedback Displays the 2nd PID feedback value if differential feedback is used (H3-
oo
= 16).
10 V: 100%
0.01%
U5-06
(7D3)
PID Adjusted Feedback
Displays the difference of both feedback values if differential feedback is
used (U5-01 - U5-05). If differential feedback is not used, then U5-01 and
U5-06 will be the same.
10 V: 100%
0.01%
U5-14
(86B)
PI Output 2 Upper 4 Digits
Displays the custom PI output.
U5-14 shows the upper 4 digits while U5-15 shows the lower 4 digits.
Monitors are scaled by b5-43 and b5-44
No signal output
available
1
U5-15
(86C)
PI Output 2 Lower 4 Digits
Displays the custom PI output.
U5-14 shows the upper 4 digits while U5-15 shows the lower 4 digits.
Monitors are scaled by b5-43 and b5-44.
No signal output
available
0.01
U5-17
(86E)
PI2 Setpoint
Displays the secondary PI setpoint.
Dependent upon S3-02
U5-18
(86F)
PI2 Feedback
Displays the secondary PI feedback value.
Dependent upon S3-02
U5-19
(870)
PI2 Input
Displays the secondary PI input (deviation between PI target and feedback). Dependent upon S3-02
U5-20
(871)
PI2 Output
Displays the secondary PI control output.
Dependent upon S3-02
U5-30
(3000)
Time Hr Min HHMM
Displays the current time (Hours and Minutes).
No signal output
available
1
U5-31
(3001)
Date Year
Displays the current year.
No signal output
available
1
U5-32
(3002)
Date Mo Day MMDD
Displays the current date (Month and Day).
No signal output
available
1
U5-33
(3003)
Date Week 000W
Displays the current date of the week.
0: Sunday
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
No signal output
available
1
U5-99
(1599)
PID Setpoint Command
Displays the PID Setpoint commanded by the source.
No signal output
available
0.01%
<1> Unit, range and resolution is determined by b5-20, b5-38, b5-39, and b5-46
<2> Unit is determined by b5-41
<3> Unit is determined by S3-04.
u
U6: Operation Status Monitors
No.
(Addr.
Hex)
Name
Description
Analog Output Level
Unit
U6-01
(51)
Motor Secondary Current
(Iq)
Displays the value of the motor secondary current (Iq). Motor rated
secondary current is 100%.
10 V: Motor secondary
rated current
0.1%
Note:
Fault histories are not kept when CPF00, CPF01, CPF06, CPF24, oFA00, oFb00, oFC00, Uv1, Uv2, or Uv3 occur.
B.12 U: Monitors
YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide
233
B
Parameter List
Summary of Contents for P1000
Page 255: ......