![YASKAWA P1000 Quick Start Manual Download Page 208](http://html1.mh-extra.com/html/yaskawa/p1000/p1000_quick-start-manual_3559550208.webp)
H3 Multi-Function Analog Input Settings
H3-
oo
Setting
Function
Description
Page
6
DC Injection Braking current
10 V = Drive rated current
–
7
Overtorque/undertorque
detection level
10 V = Drive rated current (V/f)
–
8
Stall Prevention level during run
10 V = Drive rated current
–
9
Output frequency lower limit level
10 V = E1-04 (maximum output frequency)
–
B
PID feedback
10 V = 100%
–
C
PID setpoint
10 V = 100%
–
D
Frequency bias
10 V = E1-04 (maximum output frequency)
–
E
Motor Temperature (PTC Input)
10 V = 100%
Note:
A 12 k
Ω
resistor must be connected between one of the terminals A1, A2,
or A3 and V+ for PTC functionality. Connect the 12 kOhm resistor to the
same terminal as the PTC input. Do not connect terminals V+ to AC, or
damage to the drive may result.
–
16
Differential PID feedback
10 V = 100%
–
17
Motor Thermistor (NTC)
10 V = -9 °C
0 V = 234 °C
–
1F
Through mode
Set this value when using the terminal in the pass-through mode.
–
25
Secondary PI Setpoint
10 V = S3-02 (maximum output frequency)
–
26
Secondary PI Feedback
10 V = S3-02 (maximum output frequency)
–
u
H4: Analog Outputs
No.
(Addr.
Hex)
Name
Description
Values
Page
H4-01
(41D)
Multi-Function Analog
Output Terminal FM
Monitor Selection
Selects the data to be output through multi-function analog output terminal
FM.
Set the desired monitor parameter to the digits available in U
o
-
oo
.
For example, enter “103” for U1-03.
Default: 102
Range: 000 to 999
H4-02
(41E)
Multi-Function Analog
Output Terminal FM Gain
Sets the signal level at terminal FM that is equal to 100% of the selected
monitor value.
Default: 100.0%
Min.: -999.9
Max.: 999.9
H4-03
(41F)
Multi-Function Analog
Output Terminal FM Bias
Sets the signal level at terminal FM that is equal to 0% of the selected monitor
value.
Default: 0.0%
Min.: -999.9
Max.: 999.9
H4-04
(420)
Multi-Function Analog
Output Terminal AM
Monitor Selection
Selects the data to be output through multi-function analog output terminal
AM.
Set the desired monitor parameter to the digits available in U
o
-
oo
.
For example, enter “103” for U1-03.
Default: 103
Range: 000 to 999
H4-05
(421)
Multi-Function Analog
Output Terminal AM Gain
Sets the signal level at terminal AM that is equal to 100% of the selected
monitor value.
Default: 50.0%
Min.: -999.9
Max.: 999.9
H4-06
(422)
Multi-Function Analog
Output Terminal AM Bias
Sets the signal level at terminal AM that is equal to 0% of the selected monitor
value.
Default: 0.0%
Min.: -999.9
Max.: 999.9
H4-07
(423)
Multi-Function Analog
Output Terminal FM Signal
Level Selection
0: 0 to 10 V
1: -10 to 10 V
2: 4 to 20mA
Default: 0
Range: 0 to 2
H4-08
(424)
Multi-Function Analog
Output Terminal AM Signal
Level Selection
0: 0 to 10 V
1: -10 to 10 V
2: 4 to 20 mA
Default: 0
Range: 0 to 2
B.6 H Parameters: Multi-Function Terminals
208
YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide
Summary of Contents for P1000
Page 255: ......