u
Three-Phase 600 V Class Drive Models 5A0125 to 5A0242
Table A.9 Power Ratings Continued (Three-Phase 600 V Class)
Item
Specification
Drive Models
5A0125
5A0145
5A0192
5A0242
Maximum Applicable Motor Capacity (HP)
ND Rating
125
150
200
250
Input
Input Current (A)
ND Rating
129
158
228
263
Rated Voltage
Rated Frequency
Three-phase 500 to 600 Vac 50/60 Hz
Allowable Voltage Fluctuation
-10 (-15) to +10%
Allowable Frequency Fluctuation
±5%
Input Power (kVA)
ND Rating
147
181
261
301
Output
Rated Output Capacity (kVA)
ND Rating
124
144
191
241
Rated Output Current (A)
ND Rating
125
145
192
242
Overload Tolerance
ND Rating: 120% of rated output current for 60 s
(Derating may be required for applications that start and stop frequently)
Carrier Frequency
User-adjustable between 1 and 3 kHz
Maximum Output Voltage (V)
Three-phase 500 to 600 V (proportional to input voltage)
Maximum Output Frequency (Hz)
400 Hz (user-set)
connections, and power supply impedance.
<3> Rated motor capacity is calculated with a rated output voltage of 575 V.
<4> Carrier frequency default setting is Swing PWM 1 (C6-02 = 7). C6-02 settings 1, 7, 8, 9, and A do not require current derating. All other settings
raise the carrier frequency and require current derating.