Default Values for Fan and Pump Applications
Table 4.35 Fan and Pump Application Defaults
A1-03 Setting
Parameter
8008
8009
8010
8011
A1-02
0: V/f Control
0: V/f Control
0: V/f Control
0: V/f Control
b1-04
–
–
1: Reverse Disabled
1: Reverse Disabled
b3-05
–
–
10.0 s
10.0 s
b5-01
–
1: PID Enabled
–
1: PID Enabled
b5-03
–
–
–
5.0 s
b5-08
–
–
–
2.00 s
b5-13
–
–
–
2%
b5-14
–
–
–
25.0 s
b5-18
–
1: Enabled (b5-19)
–
1: Enabled (b5-19)
b5-20
–
3: User Set
–
3: User Set
b5-46
–
–
–
1: PSI
b5-89
–
1: EZ Sleep/Wake Up
–
1: EZ Sleep/Wake Up
C1-01
–
–
90.0 s
60.0 s
C1-02
–
–
90.0 s
60.0 s
C2-01
–
–
5.00 s
5.00 s
C2-02
–
–
5.00 s
5.00 s
C2-03
–
–
5.00 s
5.00 s
C2-04
–
–
5.00 s
5.00 s
H3-10
–
B: PID Feedback
B: PID Feedback
L2-01
2: CPU Active
2: CPU Active
2: CPU Active
2: CPU Active
L3-02
–
–
110%
110%
L3-06
–
–
100%
100%
L4-05
–
–
0: Stop
–
L5-04
–
–
180.0 s
180.0 s
L5-05
1: L5-04 Interval
1: L5-04 Interval
1: L5-04 Interval
1: L5-04 Interval
o1-06
–
1: Selectable
–
1: Selectable
o1-07
–
102: Output Frequency
–
102: Output Frequency
o1-08
–
501: Feedback
–
501: Feedback
4.11 Fan and Pump Application Presets