Setup
2.5 System Configuration
2-6
169861-1CD
HW1482771
Weldcom Function: Arc
Welding Digital I/F
2.5.1 I/O Module Setting Check after Changing EW Board Station Number
Setting
The EW board removal and station number change performed in the
section 2.3 “Setting and Confirmation of Hardware Configuration”
changes the I/O module setting. The setting changes must be recognized
with [Setting] in the maintenance mode.
1. Start the DX200 while pressing [MAIN MENU]
– Start the DX200 in maintenance mode.
2. Select {SYSTEM}
→
{SECURITY}
→
“MANAGEMENT MODE”.
– A password must be entered after selecting “MANAGEMENT
MODE”.
3. Select {SYSTEM}
→
{SETUP}
→
“IO MODULE”.
4. Press the [ENTER] to check the I/O module connection status.
– If no EW board is connected, the board column displays “NONE” as
follows.
5. A confirmation dialog box appears. Select {YES}.
2.5.2 Setting of Optional Function “Network Function”
The WELDCOM function uses the network function (optional function).
Set the network function by following the procedure below.