5 Start Up
EN 32
YASKAWA Europe
TOEP C710606 50B - AC Drive L1000V - Quick Start Guide
Speed Selection
When d1-18 = 1 or 2, Multi-function digital inputs are preset as shown below.
Depending on the speed selection functions assigned to the digital inputs (H1-
settings),
the different speed levels can be selected as shown in the table below.
Terminal
Parameter
Number
Set Value
Details
S3
H1-03
50
Nominal speed (d1-19)
S4
H1-04
51
Intermediate speed 1 (d1-20)
S5
H1-05
52
Releveling speed (d1-23)
S6
H1-06
53
Leveling speed (d1-26)
Selected Speed
Leveling and Nominal
Speed assigned (H1-
50
and H1-
53)
0 = Off, 1 = On
A: No influence when d1-18=1, 0 when d1-18=2
B: No influence
N/A = Not available
Leveling speed not
assigned
(H1-
53)
Nominal Speed not
assigned
(H1-
50)
50
51
52
53
50
51
52
51
52
53
Nominal Speed (d1-19)
1
0
0
A
1
0
0
0
0
0
Intermediate Speed 1 (d1-20)
0
1
0
A
0
1
0
1
0
0
Intermediate Speed 2 (d1-21)
1
1
1
A
1
1
1
N/A
N/A
N/A
Intermediate Speed 3 (d1-22)
0
1
1
A
0
1
1
1
1
0
Revelling Speed (d1-23)
0
0
1
A
0
0
1
0
1
0
Leveling Speed (d1-26)
0
0
0
1
0
0
0
X
X
1
Zero Speed
0
0
0
0
N/A
N/A
N/A
N/A
N/A
N/A