Up and Down Commands and Speed Reference Selection
Speed Reference Selection
The speed reference selection is fixed to speed parameters d1-
and digital inputs are
used to switch between different reference values.
Up / Down Command Source Selection
The input for the Up and Down signal can be selected with parameter b1-02.
Travel Start and Stop
Travel Start
To start the elevator in up or down direction, the following conditions must be fulfilled:
• A speed reference greater than zero must be selected.
• The Safe Disable signals at terminal H1 must be closed.
• An Up or Down Signal must be set at the source specified in b1-02.
Travel Stop
The drive stops under the following conditions:
• The Up or Down command is cleared.
• d1-18 is set to 1 or 2 and the Up/Down or Leveling Speed signal (H1-
= 53) is
cleared.
• A fault occurs. The stopping method depends on the fault and certain parameter settings.
• The Safe Disable input is opened or a Base Block signal is input. In this case the brake is
closed immediately and the drive output shuts off.
Speed Selection Using Digital Inputs (b1-01 = 0)
Use parameter d1-18 to determine how different travel speeds are selected by digital inputs.
b1-02
Up/Down source
Run command input
0
Operator keypad
RUN and STOP keys on the operator
1 (default)
Digital inputs
Terminal S1: Run in Up direction
Terminal S2: Run in Down direction
d1-18
Speed Selection
0
Multi-speed inputs 1, Speed references are set in d1-01 to d1-08
1 (default)
Separate speed inputs, Speed references are set in d1-19 to d1-24 and d1-26, Higher speed has priority
2
Separate speed inputs, Speed references are set in d1-19 to d1-24 and d1-26, Leveling speed has priority