7 BACnet/IP Objects Supported

26

YASKAWA

SIEP C730600 0MA BACnet/IP Technical Manual

Object ID

Object Name

(Network Display, if Different)

Modbus Register (Hex.)

Range

Unit

PV Access

Bit 2: Reserved

Bit 3: Reserved

Bit 4: PI2 Target Input

Bit 5 to B: Reserved

Bit C: Multi-Function Input 5

Bit D: Multi-Function Input 6

Bit E: Multi-Function Input 7

Bit F: Reserved

Note:

When you use AV5, you must not use
AV1, BO4, or BV9 to BV11.

AV6

System Status

Bit 0: During Run (drive or bypass)

Bit 1: During Reverse

Bit 2: System Ready

Bit 3: System Faulted

Bit 4: Data Setting Error

Bit 5: Multi-Function Digital Output 1
(terminal M1-M2)

Bit 6: Multi-FunctionDigital Output 2
(terminal M5-M6)

Bit 7: Multi-FunctionDigital Output 3
(terminal M5-M6)
(Z1000U: MD-ME-MF)

Bit 8 to D: Reserved

Bit E: ComRef status

Bit F: ComCtrl status

0020

0 - 65535

Bitmap

R

AV7

Fault Details

Bit 0: oC [Overcurrent], GF [Ground
Fault]

Bit 1: ov [Overvoltage]

Bit 2: oL2 [Drive Overload]

Bit 3: oH1 [Heatsink Overheat], oH2
[External Overheat (H1-XX=B)]

Bit 4 to 6: Reserved

Bit 7: EF to EF7 [External Fault]

Bit 8: CPFxx [Hardware Fault]
(includes oFAxx)

Bit 9: oL1 [Motor Overload], oL3
[Overtorque Detection 1], UL3
[Undertorque Detection 1]

Bit A: Reserved

Bit B: Uv [Undervoltage]

Bit C: Uv1 [DC Bus Undervoltage],
Uv2 [Control Power Undervoltage],
Uv3 [Soft Charge Answerback Fault]

Bit D: LF [Output Phase Loss], PF
[Input Phase Loss]

Bit E: CE [Modbus Communication
Error], bUS [Option Communication
Error]

Bit F: oPr [Keypad Connection Fault]

0021

0 - 65535

Bitmap

R

AV8

Data Link Status

Bit 0: Writing Data

Bit 1: Reserved

Bit 2: Reserved

Bit 3: Upper or lower limit error

Bit 4: Data conformity error

Bit 5: Writing to EEPROM

Bit 6 to F: Reserved

0022

0 - 63

Bitmap

R

AV9

Frequency Reference

0040

0 - 600.00

Determined by o1-03

R

AV10

Output Frequency

0041

0 - 600.00

Determined by o1-03

R

AV11

Output Voltage

0045

0 - 6553.5

V

R

AV12

Output Current

0026

0 - 6553.5

A

R

AV13

Output Power

0047

0 - 6553.5 > 11 kVA

0 - 655.35 ≤ 11 kVA

KW

R

AV14

*3

Torque Reference

0048

0 - 100.0

%

R

AV15

Drive Multi-Function Input Status

(MF Input Status)

002B

0 - 255

Bitmap

R

AV16

Drive Status 2

002C

0 - 65535

Bitmap

R

Summary of Contents for JOHB-SMP3

Page 1: ...SKAWA AC Drive Option BACnet IP Technical Manual Model JOHB SMP3 To correctly use the product read this manual thoroughly and keep it for easy reference inspection and maintenance Make sure that the e...

Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEP C730600 0MA BACnet IP Technical Manual...

Page 3: ...ption LED States 9 Power Up Diagnostics 10 5 Installation Procedure 10 Section Safety 10 Settings for DIP Switch S1 11 Procedures to Install and Wire the Option 11 Procedure A 11 Procedure B 13 Proced...

Page 4: ...y Login 39 Webpage Password 39 Webpage Settings 40 Email Settings 40 9 Troubleshooting 40 Drive Side Error Codes 40 Faults 40 Minor Faults and Alarms 41 bUS Fault Tolerance 41 bUS Fault Auto Restart 4...

Page 5: ...gether with the product YASKAWA AC Drive Option BACnet IP Technical Manual Manual No SIEP C730600 0M This book The technical manual contains detailed information about the option Access the following...

Page 6: ...equipment WARNING Electrical Shock Hazard Do not modify the drive or option circuitry Failure to obey can cause serious injury or death or cause damage to the drive or option and will void warranty Y...

Page 7: ...shipping If there is damage to the option or other parts contact the shipping company immediately NOTICE Damage to Equipment Do not use damaged parts to connect the drive and the option Failure to com...

Page 8: ...crew sizes are different for different drive capacities Prepare different screwdrivers for different screw sizes 4 Option Components Option Components A Connector CN5 B Installation hole C LED NS 1 D...

Page 9: ...of the option LEDs after the power up diagnostic LED sequence is complete Refer to Table 4 3 for more information about the LEDs Table 4 2 Option LED States LED Name Indication Operating State Descrip...

Page 10: ...operate the drive Use the drive only as specified by the instructions Some figures in this section include drives without covers or safety shields to more clearly show the inside of the drive If cover...

Page 11: ...h S1 Note If you set the DIP switch for a different protocol it will erase all user entered data from the JOHB SMP3 including the Device Object Name Procedures to Install and Wire the Option Procedure...

Page 12: ...nstall this option into the CN5 A connector on the drive control board 1 Shut off power to the drive and wait for the time specified on the drive warning label at a minimum Make sure that the charge i...

Page 13: ...m main circuit wiring and other electrical and power lines Make sure that you firmly connect the cable end Refer to Communication Cable Specifications on page 17 for more information 8 Reattach the fr...

Page 14: ...the drive is de energized The charge indicator LED extinguishes when the DC bus voltage decreases below 50 Vdc When all indicators are OFF measure for dangerous voltages to make sure that the drive i...

Page 15: ...cal and power lines Make sure that you firmly connect the cable end Refer to Communication Cable Specifications on page 17 for more information 9 Reattach the drive front cover E and the keypad F Refe...

Page 16: ...er supplied network cable into the CN1 connection port on the option board When you have a dual port option connect two network cables to the two network ports in CN1 for flexibility in cabling topolo...

Page 17: ...y Daisy Chained Use the communication connectors CN1A Port 1 and CN1B Port 2 at the same time A switch is not necessary for this connection Note This option does not support STP Spanning Tree Protocol...

Page 18: ...op Use C1 09 3 Alarm Only 4 Alarm Run at d1 04 5 Alarm Ramp Stop Note When you set this parameter to 3 or 4 the drive will continue operation after it detects a fault Separately prepare safety protect...

Page 19: ...the BACnet Device Object Example 1 Set the Device Object Instance Identifier to 1234 1234 decimal is equal to 4D2 Hex Set F6 48 4D2 Hex and F6 49 0 Hex Example 2 Set the Device Object Instance Identi...

Page 20: ...ers Reload Reload Now enables communication OPT parameter changes without turning on the power again 192 0 255 F7 10 03EE Gateway Address 2 Sets the static fixed Gateway address Sets the second most s...

Page 21: ...Broadcast Management Device BBMD to which the drive will register as a foreign device 0 0 255 F7 53 1BEB BBMD Foreign Register Addr 3 Sets the third octet of the IP Address of the BACnet Broadcast Man...

Page 22: ...tet U4 81 Fifth octet Sixth octet Note Not all drive software versions will display this monitor Contact Yaskawa or your nearest sales representative for more information This monitor is not available...

Page 23: ...ring Change Of Value Property B Client DM DDB B Device Management Dynamic Device Binding B Client DM DOB B Device Management Dynamic Object Binding B Client DM DCC B Device Management Device Communica...

Page 24: ...Yes Yes Yes Yes Yes Polarity Yes Yes Present_Value Yes Yes Yes Yes Yes Yes Priority_Array Yes 2 Yes 2 Yes Yes 2 Property_List Yes Yes Yes Yes Yes Yes Yes Protocol_Object_Types_Supported Yes Protocol_...

Page 25: ...FM set H4 01 0 Drv Anlg Out1 Level 0007 0 100 0 C AO2 1 Drive Analog Output 2 Level Drive Terminal AM set H4 01 0 Drv Anlg Out2 Level 0008 0 100 0 C 1 Not available on all drives Refer to the Technic...

Page 26: ...sink Overheat oH2 External Overheat H1 XX B Bit 4 to 6 Reserved Bit 7 EF to EF7 External Fault Bit 8 CPFxx Hardware Fault includes oFAxx Bit 9 oL1 Motor Overload oL3 Overtorque Detection 1 UL3 Underto...

Page 27: ...11 kVA A R AV32 2 120V to Kx Coils 8790 0 65535 V R AV33 Drive kWh consumed kWh consumed 005C 005D 0820 0822 for Z1000U 0 999999999 kWh R AV34 Drive kWh Regenerated kWh Regenerated Z1000U only 0823 0...

Page 28: ...Not available on all drives Refer to the Technical Manual of your drive and check if the Modbus register of the applicable object exists 4 See Gateway Mode features in drive manuals for use instructio...

Page 29: ...f HW Status Saf Trq Off Hw Stat 0020 Bit 12 ALARM OK R BI32 2 Safe Torque Off Status Saf Trq Off Stat 0020 Bit 13 ALARM OK R 1 Available on bypass only 2 Not available on Z1000U Binary Output Objects...

Page 30: ...20 Bit 3 FAULTED OFF R BV17 Data Set Error 004B Bit 8 ERROR OFF R BV18 Overcurrent Ground Fault Overcurrent Gnd Flt 0021 Bit 0 OC GF OFF R BV19 Main Circuit Overvoltage Main Ckt Overvoltage 0021 Bit 1...

Page 31: ...400 Bit 4 ON OFF C BV63 6 Emergency Override Drive Forward Em Over DRV FWD CMD Internal ON OFF C BV64 8 Bypass Motor OR Select Command BYP Mtr OR Sel CMD 8400 Bit 6 ON OFF C BV65 8 Bypass Motor AND Se...

Page 32: ...atus BYP Motor 2 Sel Stat 8785 Bit 7 SELECT OFF R BV96 8 Bypass Drive Fault Status BYP Drive Flt Status 8786 Bit 0 FAULT OFF R BV97 8 BYP Safety Status 2 BYP Safety Status 2 8786 Bit 1 OPEN CLOSED R B...

Page 33: ...9xxxx Number of APDU Retries 0 fixed Object Identifier Instance Numeric value set by F6 49 and F6 48 Type OBJECT_DEVICE fixed Object List List of all available objects Object Name Settable via the net...

Page 34: ...er Quality Network Type 5 IPV4 fixed Object Identifier Instance 1 fixed Type OBJECT_NETWORK_PORT 1 fixed Object Type 56 Object Network Port fixed Out Of Service FALSE fixed Protocol Level 2 BACnet App...

Page 35: ...Web Interface YASKAWA SIEP C730600 0MA BACnet IP Technical Manual 35 Figure 8 1 Home Page View BACnet IP Page The BACnet IP page shows basic information about the protocol Figure 8 2 BACnet IP Page Vi...

Page 36: ...ns Duplex Display either Full or Half Excessive Collisions Cumulative number of excessive collisions FCS Errors Cumulative number of frame check sequence errors Frame Too Large Cumulative number of fr...

Page 37: ...ulative number of non unicast packets sent Out Octets Cumulative number of outgoing octets Out Ucast Packets Cumulative number of unicast packets sent Single Collisions Cumulative number of single col...

Page 38: ...cing emails about reoccurring errors Click Save Email Settings when you save the entered information into the option Figure 8 5 Email Alerts Page View Procedure Conditional Email Set up 1 Click the En...

Page 39: ...nished Settings Page Requires Security Login The Settings page sets web page behavior parameters Access is restricted unless a valid password is entered The default password is yaskawa Figure 8 7 Sett...

Page 40: ...ive did not receive a signal from the controller The communications cable wiring is incorrect Check for wiring errors Correct the wiring An existing short circuit or communications disconnection Check...

Page 41: ...ion DIP switch S1 as shown in page 11 Monitor U4 75 Communication OPT Protocol will display the DIP switch S1 setting BACnet IP is not installed on the JOHB SMP3 card Upgrade the software in the JOHB...

Page 42: ...guration bUS 1106 F7 13 0 Address Mode at Startup Static is set and F7 01 to F7 12 IPAddress 1 to 4 Subnet Mask 1 to 4 Gateway Address 1 to 4 are set to an invalid configuration Set the parameters to...

Page 43: ...required for engaging in business and commerce in Europe This option displays the CE mark based on the EMC Directive 2014 30 EU Drives used in combination with this option and devices used in combinat...

Page 44: ...shield to the metal panel according to Figure 10 2 Figure 10 3 and Figure 10 4 Figure 10 2 Option Installation for CE Compliance Z1000U Figure 10 3 Option Installation for CE Compliance HV600 Figure...

Page 45: ...mestic environment Note The user guide applies only to Business Broadcasting Communication Equipment Comply with the EMC Directive to conform to the Korean Radio Act 12 Specifications Specifications T...

Page 46: ...dardized Device Profile Annex L BACnet Cross Domain Advanced Operator Workstation B XAWS BACnet Advanced Operator Workstation B AWS BACnet Operator Workstation B OWS BACnet Operator Display B OD BACne...

Page 47: ...Output Object Binary Value Object Data Link Layer Options ARCNET ATA 878 1 2 5 Mb Clause 8 ARCNET ATA 878 1 EIA 485 Clause 8 baud rate s BACnet IP Annex J BACnet IP Annex J BACnet Broadcast Management...

Page 48: ...way Network Security Options Non secure Device is capable of operating without BACnet Network Security Secure Device is capable of using BACnet Network Security NS SD BIBB Multiple Application Specifi...

Page 49: ...YASKAWA SIEP C730600 0MA BACnet IP Technical Manual 49 Revision History Date of Publication Revision Number Section Revised Content October 2022 First Edition...

Page 50: ...Piraporinha Diadema S o Paulo 09950 000 Brasil Phone 55 11 3585 1100 Fax 55 11 3585 1187 www yaskawa com br YASKAWA EUROPE GmbH Hauptstra e 185 65760 Eschborn Germany Phone 49 6196 569 300 Fax 49 619...

Reviews: