24
YASKAWA
SIEP C730600 0MA BACnet/IP Technical Manual
Property
Object Type
Device
Analog Input
(AI)
Analog
Output
(AO)
Analog Value
(AV)
Binary Input
(BI)
Binary
Output
(BO)
Binary Value
(BV)
Current_Command_Priority
-
-
Yes
Yes
-
Yes
Yes
Database_Revision
Yes
-
-
-
-
-
-
Daylight_Savings_Status
Yes
-
-
-
-
-
-
Device_Address_Binding
Yes
-
-
-
-
-
-
Event_State
-
Yes
Yes
Yes
Yes
Yes
Yes
Firmware_Revision
Yes
-
-
-
-
-
-
Inactive_Text
-
-
-
-
Yes
Yes
Yes
Local Date
Yes
-
-
-
-
-
-
Local Time
Yes
-
-
-
-
-
-
Location
Yes
-
-
-
-
-
-
Max_APDU_Length_Accepted
Yes
-
-
-
-
-
-
Model_Name
Yes
-
-
-
-
-
-
Number_Of_APDU_Retries
Yes
-
-
-
-
-
-
Object_Identifier
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Object_List
Yes
-
-
-
-
-
-
Object_Name
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Object_Type
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Out_Of_Service
-
Yes
Yes
Yes
Yes
Yes
Yes
Polarity
-
-
-
-
Yes
Yes
-
Present_Value
-
Yes
Yes
Yes
Yes
Yes
Yes
Priority_Array
-
-
Yes
Yes
-
Yes
Yes
Property_List
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Protocol_Object_Types_Supported
Yes
-
-
-
-
-
-
Protocol_Revision
Yes
-
-
-
-
-
-
Protocol_Services_Supported
Yes
-
-
-
-
-
-
Protocol_Version
Yes
-
-
-
-
-
-
Reliability
-
-
-
-
-
-
-
Relinquish_Default
-
-
Yes
Yes
-
Yes
Yes
Segmentation_Supported
-
-
-
-
-
-
-
Status_Flags
-
Yes
Yes
Yes
Yes
Yes
Yes
System_Status
Yes
-
-
-
-
-
-
Units
-
Yes
Yes
Yes
-
-
-
UTC_Offset
Yes
-
-
-
-
-
-
Vendor_Identifier
Yes
-
-
-
-
-
-
Vendor_Name
Yes
-
-
-
-
-
-
*1
COV function is only available on objects that are not commandable and not writable.
*2
For Commandable Object Instances only.
◆
Analog Input Objects
Object ID
Object Name
(Network Display, if Different)
Modbus Register (Hex.)
Range
Unit
PV Access
AI1
Drive Analog Input 1 Level
(Drv Anlg In 1 Level)
004E
0 - 100.0
%
R
AI2
Drive Analog Input 2 Level
(Drv Anlg In 2 Level)
004F
0 - 100.0
%
R
AI3
Drive Analog Input 3 Level
0050
0 - 100.0
%
R