38
YASKAWA
SIEP C730600 0MA BACnet/IP Technical Manual
◆
Email Alerts Page (Requires Security Login)
The Email Alerts page allows the user to configure four Email Fault/Alarm conditions. When the condition is true,
one email will be sent to the provided email address. Another email will not be sent until the condition becomes
false and then true again. A 30-second timer prevents emails from being sent when conditions reoccur
immediately after being removed. The timer helps limit the amount of emails sent regarding the same intermittent
condition and helps to reduce network traffic by reducing emails about reoccurring errors.
Click
“
Save Email Settings
”
when you save the entered information into the option.
Figure 8.5 Email Alerts Page View
■
Procedure: Conditional Email Set-up
1.
Click the “Enable” check box to enable the alert.
2.
Define the condition that will trigger the email by selecting a monitor parameter, a comparator, and a
value.
Set the conditions to send alerts from the “Condition” drop-down selection. If choosing only one condition
and no OR or AND are needed, set the “OR/AND” drop-down selection to “—”.
3.
Enter the email address where the alert will be sent.
4.
Enter the message that will appear in the email contents.
5.
Enter the email subject.
◆
Parameter Access Page (Requires Security Login)
The Parameter Access page lets you read parameters, monitors and other Memobus registers from the drive.