SIEP C730600 0MA BACnet/IP Technical Manual
33
*9
Set
Z1-39 = 3
to use.
*10
Set
Z3-12 = 1
to use. Use with caution because objects BV72 to BV81 will be logically ORed with the physical digital inputs. This
can cause hard-wired Normally Closed inputs (for example, Safety or Interlock) to operate incorrectly.
◆
Device Object
Table 7.4 Device Objects
Property
Description
Active COV Subscriptions
Contains a list of all active COV subscriptions
APDU Timeout
10000 milliseconds (fixed)
Application Software Version
“
VST9070xx
”
(fixed)
Database Revision
0
Daylight Savings Status
TRUE or FALSE
Device Address Binding
-
Firmware Revision
3.0x (fixed)
Local Date
Read from the drive (if available).
Can also be set over the network.
Local Time
Read from the drive (if available).
Can also be set over the network.
Location
Settable via the network. If not set, it will default to the drive model number and serial number.
Example:
“
CIPR-HV60U4005 S/N:1W221325769xxxx
”
Max APDU Length Accepted
1476 bytes (fixed)
Model Name
Drive model number and serial number.
Example:
“
CIPR-HV60U4005 S/N:1W221325769xxxx
”
Number of APDU Retries
0 (fixed)
Object Identifier
Instance: Numeric value set by F6-49 and F6-48
Type:
“
OBJECT_DEVICE
”
(fixed)
Object List
<List of all available objects>
Object Name
Settable via the network. If not set, it will default to:
“
Yaskawa
”
+
“
VFD
”
or BYP
”
+
“
ID
”
+ F6-49 (Hex.) + F6-48 (Hex.)
Example:
“
Yaskawa VFD ID092A5A
”
Object Type
8: Object Device (fixed)
Protocol Object Types Supported
Analog Input, Analog Output, Analog Value, Binary Input, Binary Output, Binary Value, Device, Network Port
Protocol Revision
19 (fixed)
Protocol Services Supported
Subscribe COV, Read Property, Read Property Multiple, Write Property, Write Property Multiple, Device Communication
Control, Reinitialize Device, Time Synchronization, Who Has, Who Is, UTC Time Synchronization, Subscribe COV
Property
Protocol Version
1 (fixed)
Segmentation Supported
3: None
System Status
0: Operational
4: Non Operational (faulted)
UTC Offset
Settable from the network. Units are
“
minutes
”
.
Vendor Identifier
141 (fixed)
Vendor Name
Yaskawa (fixed)
◆
Network Port Object
Table 7.5 Network Port Objects
Property
Description
APDU Length
1476 (fixed)
BACnet IP Mode
0: Normal or 1: Foreign
BACnet IP UDP Port
Set by F7-50
Changes Pending
TRUE or FALSE
Foreign Device BBMD Address
Settable over network or using drive parameters:
IP Address: Set by F7-51 to F7-54
Port: Set by F7-55