1.22 Defaults by o2-04 [Drive Model (kVA) Selection]
YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
153
Name
Unit
Default
-
Drive Model
-
2011
2017
2024
2031
2046
2059
2075
2088
o2-04
Drive Model
(KVA)
Selection
Hex.
65
67
68
6A
6B
6D
6E
6F
E2-11
(E4-11, E5-
02)
Motor Rated
Power
HP
(kW)
3
(2.2)
5
(3.7)
7.5
(5.5)
10
(7.5)
15
(11)
20
(15)
25
(18.5)
30
(22)
L2-05
Undervoltage
Detection Lvl
(Uv1)
-
190
190
190
190
190
190
190
190
L3-24
Motor Accel
Time for
Inertia Cal
s
0.145
0.154
0.168
0.175
0.265
0.244
0.317
0.355
L8-02
Overheat
Alarm Level
°C
95
95
125
125
125
125
115
115
L8-09
Output Ground
Fault
Detection
-
0
0
0
0
0
1
1
1
L8-35
Installation
Method
Selection
-
2
2
2
2
2
2
L8-38
Carrier
Frequency
Reduction
-
2
2
2
2
2
2
2
2
n1-01
Hunting
Prevention
Selection
-
1
1
1
1
1
1
1
1
n1-03
Hunting
Prevention
Time Constant
ms
10
10
10
10
10
10
10
10
*1
Parameters within parentheses are for motor 2.
*2
You can use this parameter only when
A1-02 = 0 [Control Method Selection = V/f]
.
*3
When you use an IP55/UL Type 12 drive, the factory default setting is
3 [IP55/UL Type 12]
.
No.
Name
Unit
Default
-
Drive Model
-
2114
2143
2169
2211
2273
o2-04
Drive Model (KVA)
Selection
Hex.
70
72
73
74
75
E2-11
(E4-11, E5-02)
Motor Rated
Power
HP
(kW)
40
(30)
50
(37)
60
(45)
75
(55)
100
(75)
b3-04
V/f Gain during
Speed Search
%
80
80
80
80
80
b3-06
Speed Estimation
Current Level 1
-
0.5
0.5
0.5
0.5
0.7
b3-08
Speed Estimation
ACR P Gain
-
0.50
0.50
0.50
0.50
0.50
b3-11
Spd Est Method
Switch-over Level
%
5.0
5.0
5.0
5.0
5.0
b3-12
Speed Search
Current Deadband
-
2.5
2.5
2.5
2.5
2.5
b3-26
Direction
Determination Level
-
1000
1000
1000
1000
1000
b8-04
Energy Saving
Coefficient Value
-
46.27
38.16
35.78
31.35
23.10
C6-02
Carrier Frequency
Selection
-
2
2
2
2
2
E2-01
(E4-01)
Motor Rated Current
(FLA)
A
114
143
169
211
273
E2-02
(E4-02)
Motor Rated Slip
Hz
1.80
1.33
1.60
1.43
1.39
E2-03
(E4-03)
Motor No-Load
Current
A
21.9
38.2
44.0
45.6
72.0