1.22 Defaults by o2-04 [Drive Model (kVA) Selection]
154
YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
No.
Name
Unit
Default
-
Drive Model
-
2114
2143
2169
2211
2273
o2-04
Drive Model (KVA)
Selection
Hex.
70
72
73
74
75
E2-11
(E4-11, E5-02)
Motor Rated
Power
HP
(kW)
40
(30)
50
(37)
60
(45)
75
(55)
100
(75)
E2-05
(E4-05)
Motor Line-to-Line
Resistance
Ω
0.064
0.039
0.030
0.022
0.023
E2-06
(E4-06)
Motor Leakage
Inductance
%
20.8
18.8
20.2
20.5
20.0
E2-10
(E4-10)
Motor Iron Loss
W
699
823
852
960
1200
E5-01
PM Motor Code
Selection
-
FFFF
FFFF
FFFF
FFFF
FFFF
L2-02
Power Loss Ride
Through Time
s
2.0
2.0
2.0
2.0
2.0
L2-03
Minimum Baseblock
Time
s
1.1
1.1
1.2
1.3
1.5
L2-04
Powerloss V/f
Recovery Ramp
Time
s
0.6
0.6
1
1
1
L2-05
Undervoltage
Detection Lvl (Uv1)
-
190
190
190
190
190
L3-24
Motor Accel Time
for Inertia Cal
s
0.323
0.32
0.387
0.317
0.533
L8-02
Overheat Alarm
Level
°C
115
110
110
110
110
L8-09
Output Ground Fault
Detection
-
1
1
1
1
1
L8-35
Installation Method
Selection
-
2
2
0
0
Carrier Frequency
Reduction
-
2
2
2
2
2
n1-01
Hunting Prevention
Selection
-
1
1
1
1
1
n1-03
Hunting Prevention
Time Constant
ms
10
10
10
10
10
*1
Parameters within parentheses are for motor 2.
*2
You can use this parameter only when
A1-02 = 0 [Control Method Selection = V/f]
.
*3
When you use an IP55/UL Type 12 drive, the factory default setting is
3 [IP55/UL Type 12]
.
◆
480 V Class
Name
Unit
Default
-
Drive Model
-
4005
4008
4011
4014
4021
4027
4034
4040
o2-04
Drive Model
(KVA)
Selection
Hex.
95
97
99
9A
9B
9D
9E
9F
E2-11
(E4-11, E5-
02)
Motor Rated
Power
HP
(kW)
3
(2.2)
5
(3.7)
7.5
(5.5)
10
(7.5)
15
(11)
20
(15)
25
(18.5)
30
(22)
b3-04
V/f Gain
during Speed
Search
%
100
100
100
100
100
100
100
100
b3-06
Speed
Estimation
Current Level
1
-
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
b3-08
Speed
Estimation
ACR P Gain
-
0.50
0.50
0.50
0.50
0.50
0.50
0.50
0.50