1.22 Defaults by o2-04 [Drive Model (kVA) Selection]
152
YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
1.22
Defaults by o2-04 [Drive Model (kVA) Selection]
The values for parameter
o2-04
changes the default settings for the parameters in these tables:
◆
208 V Class
Name
Unit
Default
-
Drive Model
-
2011
2017
2024
2031
2046
2059
2075
2088
o2-04
Drive Model
(KVA)
Selection
Hex.
65
67
68
6A
6B
6D
6E
6F
E2-11
(E4-11, E5-
02)
Motor Rated
Power
HP
(kW)
3
(2.2)
5
(3.7)
7.5
(5.5)
10
(7.5)
15
(11)
20
(15)
25
(18.5)
30
(22)
b3-04
V/f Gain
during Speed
Search
%
100
100
100
100
100
100
100
100
b3-06
Speed
Estimation
Current Level
1
-
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
b3-08
Speed
Estimation
ACR P Gain
-
0.50
0.50
0.50
0.50
0.50
0.50
0.50
0.50
b3-11
Spd Est
Method
Switch-over
Level
%
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
b3-12
Speed Search
Current
Deadband
-
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
b3-26
Direction
Determination
Level
-
1000
1000
1000
1000
1000
1000
1000
1000
b8-04
Energy Saving
Coefficient
Value
-
156.8
122.9
94.75
72.69
70.44
63.13
57.87
51.79
C6-02
Carrier
Frequency
Selection
-
2
2
2
2
2
2
2
2
E2-01
(E4-01)
Motor Rated
Current (FLA)
A
10.6
16.7
24.2
30.8
46.2
59.4
74.8
88
E2-02
(E4-02)
Motor Rated
Slip
Hz
2.90
2.73
1.50
1.30
1.70
1.60
1.67
1.70
E2-03
(E4-03)
Motor No-
Load Current
A
3.00
4.50
5.10
8.00
11.2
15.2
15.7
18.5
E2-05
(E4-05)
Motor Line-to-
Line
Resistance
Ω
1.601
0.771
0.399
0.288
0.230
0.138
0.101
0.079
E2-06
(E4-06)
Motor
Leakage
Inductance
%
18.4
19.6
18.2
15.5
19.5
17.2
20.1
19.5
E2-10
(E4-10)
Motor Iron
Loss
W
77
112
172
262
245
272
505
538
E5-01
PM Motor
Code Selection
-
FFFF
FFFF
FFFF
FFFF
FFFF
FFFF
FFFF
FFFF
L2-02
Power Loss
Ride Through
Time
s
0.7
0.9
1.5
1.8
2.0
2.0
2.0
2.0
L2-03
Minimum
Baseblock
Time
s
0.5
0.6
0.7
0.8
0.9
1
1
1
L2-04
Powerloss V/f
Recovery
Ramp Time
s
0.3
0.3
0.3
0.3
0.3
0.6
0.6
0.6