2 Mechanical Installation
YASKAWA Europe
TOEP C710606 75B - AC Drive V1000 IP66 - Quick Start Guide
EN 11
4.
Connect the power supply cable to the EMC Filter. Use only the green colored screws for grounding. Connect motor cable to inverter main
terminals and control circuit to the control terminals.
5.
Install option cards if required. For drives CIMR-VCBA
HAA-00
and CIMR-VC4A0001HAA-00
to CIMR-VC4A0011HAA-
00
place the bottom cover and terminal cover delivered with the drive before attaching the option card.
Reattaching the Front Cover
NOTICE:
Be careful not to pinch or damage the front cover sealing when attaching the front cover. Any damage to the sealing may allow moisture or oil to enter the drive
case and damage components.
NOTICE:
Equipment Hazard. Be sure to fastening all screws in accordance with specified tightening torque. If any screws are loose, water and oil may seep into the case
and damage the drive.
1.
For drives with digital operator in the front cover insert the LED operator cable back into the correct port on the drive.
2.
Place the front cover back onto the drive, and fasten the cover screws applying the following tightening torque values:
Drives CIMR-VCBA
and CIMR-VC4A0001 to 0011: 1.5 Nm
Drives CIMR-VC4A0018 to 0038: 2.5 Nm
Cable Glands
NOTICE:
Equipment Hazard. Use only the recommended multiconductor cable and use one cable per cable gland only. Attempting to pass more than one wire through a
cable gland will result in a space between those wires, thus considerably reducing the water-proofing and dust-proofing capabilities of the cable gland, and may
result in damaging the drive.
NOTICE:
Make sure that the rubber edging along the outside of the cable gland is properly sealed. Failing to properly seal the outside may allow water or oil into the drive
and damage components.
Cable Glands Specifications and Model Numbers
YASKAWA recommends using SKINTOP cable glands by Lapp Kabel for use with V1000 Series IP66 Type.
Main Circuit Wiring
Note:
Main circuit wires should be multiconductor 600 V vinyl insulated line with a continuous maximum allowable temperature of over 70
C (such as ÖLFLEX® CLASSIC
100/100CY by Lapp Kabel).
Note:
For single phase input, use 3 wire cable, and for 3-phase input, use 4 wire cable.
Note:
Always use shielded motor cables.
Control Circuit Wiring
Note:
Main circuit wires should be multiconductor shielded line with a continuous maximum allowable temperature of over 70
C (such as ÖLFLEX® CLASSIC 110/115CY
and UNITRONIC® LiYCY (TP) by Lapp Kabel).
Drive Side Wiring Hole Diameter (mm)
<1>
<1> Separate holes have been provided for input, output, and option wiring (total of 4 holes).
<2> Note that the cable gland body and locknut are usually sold separately.
Recommended Cable Glands
(Lapp Kabel)
Drive Size
Input
Output
Input / Output Wiring
Cable Gland No./Model
<2>
Cable Diameter
(mm)
Tightening Torque
(Nm)
A
28.8
28.8
Body: 53015150/STR 21
Locknut: 53019050/GMP-GL21
9 to 16
Body: 5.0
Locknut: 7.5
Body: 53015050/ST 21
Locknut: 53019050/GMP-GL21
13 to 18
B
37
37
Body: 53015160/STR 29
Locknut: 53019060/GMP-GL29
11 to 22
Body: 5.0
Locknut: 7.5
Body: 53015060/ST 29
Locknut: 53019060/GMP-GL29
14 to 25
Drive Side Wiring Hole
<1>
<1> Sealing grommets fitted to control circuit wiring holes on reception.
<2> Note that the cable gland body and locknut are usually sold separately.
Recommended Cable Glands for I/O Wiring (Lapp Kabel)
Diameter (mm)
Number of Holes
Cable Gland No./Model
<2>
Cable Diameter (mm)
Tightening Torque (Nm)
23
2
Body: 53015140/STR 16
Locknut: 53019040/GMP-GL16
6 to 12
Body: 3.3
Locknut: 5.0
Body: 53015040/ST 16
Locknut: 53019040/GMP-GL16
9 to 14
1. Sostituite il coper-
chio inferiore.
2. Sostituite il
coperchio terminali.
3. Installare la
scheda opzionale.