background image

7  Troubleshooting

YASKAWA Europe 

TOEP C710606 75B - AC Drive V1000 IP66 - Quick Start Guide

EN  25

7

Troubleshooting

General Fault and Alarms

Faults and alarms indicate problems in the drive or in the machine.
An alarm is indicated by a code on the data display and the flashing ALM LED. The drive output is not necessarily switched off. 
A fault is indicated by a code on the data display and the ALM LED is on. The drive output is always switched off immediately and the motor coast 

to stop.
To remove an alarm or reset a fault, trace the cause, remove it and reset the drive by pushing the Reset key on the operator or cycling the power 

supply.
This lists up the most important alarms and faults only. Please refer to the Technical Manual for a complete list.

LED Display

ALM FLT

Cause

Corrective Action

Base Block

The software base block function is assigned to one of the digital inputs and 
the input is off. The drive does not accept Run commands.

• Check the digital inputs function selection.
• Check the upper controller sequence.

Control Fault

The torque limit was reached during deceleration for longer than 3 sec. 
when in Open Loop Vector control

• The load inertia is too big.
• The torque limit is too low.
• The motor parameters are wrong.

• Check the load.
• Set the torque limit to the most appropriate setting (L7-01 through L7-

04).

• Check the motor parameters.

Control Circuit Fault

There is a problem in the drive’s control circuit.

• Cycle the drive power supply.
• Initialize the drive.
• Replace the drive if the fault occurs again.

Control Circuit Fault

There is no terminal board connected to the control board or the connection 
is broken.

• Check if the terminal board is installed properly.
• Uninstall and Reapply the terminal board.
• Change the drive.

Cannot Reset

Fault reset was input when a Run command was active.

Turn off the Run command and reset the drive.

Option External Fault

An external fault was tripped by the upper controller via an option card.

• Remove the fault cause, reset the fault and restart the drive.
• Check the upper controller program.

External Fault

A forward and reverse command were input simultaneously for longer than 
500 ms. This alarm stops a running motor.

Check the sequence and make sure that the forward and reverse input are 
not set at the same time.

External Faults

• An external fault was triggered by an external device via one of the 

digital inputs S1 to S6.

• The digital inputs are set up incorrectly.

• Find out why the device tripped the EF. Remove the cause and reset the 

fault.

• Check the functions assigned to the digital inputs.

Internal Fan Alarm

• Internal stirring fan does not work

• Replace internal fan (see fig. 

Replacing the Internal Stirring Fan on 

page 28

)

Ground Fault

Ground leakage current has exceeded 50% of the drives rated output 
current.

• Cable or motor insulation is broken.
• Excessive stray capacitance at drive output.

• Check the output wiring and the motor for short circuits or broken 

insulation. Replace any broken parts.

• Reduce the carrier frequency.

Drive Disable

Both Drive Disable inputs are open. The drive output is safely disabled and 
the motor can not be started.

• Check why the upper controller’s safety device disabled the drive. 

Remove the cause and restart.

• Check the wiring. If the Drive Disable function is not utilized for 

EN60204-1, stop cat. 0 or for disabling the drive, the terminals HC, H1, 
H2 must be linked.

Drive Disable Fault

Drive output is disabled while only one of the Drive Disable inputs is open. 
(normally both input signals H1 and H2 should be open)

• One channel is internally broken and does not switch off, even if the 

external signal is removed.

• Only one channel is switched off by the upper controller.

• Check the wiring from the upper controller and make sure that both 

signals are set correctly by the controller.

• If the signals are set correctly and the alarm does not disappear, replace 

the drive.

Output Phase Loss

• Output cable is disconnected or the motor winding is damaged.
• Loose wires at the drive output.
• Motor is too small (less than 5% of drive current).

• Check the motor wiring.
• Make sure all terminal screws in the drive and motor are properly 

tightened.

• Check the motor and drive capacity.

Overcurrent

• Short circuit or ground fault on the drive output side
• The load is too heavy.
• The accel./decel. times are too short.
• Wrong motor data or V/f pattern settings.
• A magnetic contactor was switched at the output.

• Check the output wiring and the motor for short circuits or broken 

insulation. Replace the broken parts.

• Check the machine for damages (gears, etc.) and repair any broken parts.
• Check the drive parameter settings.
• Check the output contactor sequence.

Heatsink Overheat

• Surrounding temperature is too high.
• The cooling fan has stopped.

<1>

• The heatsink is dirty.
• The airflow to the heatsink is restricted.

• Check the surrounding temperature and install cooling devices if 

necessary.

• Check the drive cooling fan.
• Clean the heatsink.
• Check the airflow around the heatsink.

Motor Overload

• The motor load is too heavy.
• The motor is operated at low speed with heavy load.
• Cycle times of accel./ decel. are too short.
• Incorrect motor rated current has been set.

• Reduce the motor load.
• Use a motor with external cooling and set the correct motor in parameter 

L1-01

• Check the sequence.
• Check the rated current setting.

Drive Overload

• The load is too heavy.
• The drive capacity is too small.
• Too much torque at low speed.

• Check the load.
• Make sure that the drive is big enough to handle the load.
• The overload capability is reduced at low speeds. Reduce the load or 

increase the drive size.

DC Overvoltage

DC bus voltage rose too high.

• The deceleration time is too short.
• Stall prevention is disabled.
• Braking chopper / resistor broken.
• Unstable motor control in OLV.
• Too high input voltage.

• Increase the deceleration time.
• Enable stall prevention by parameter L3-04.
• Make sure the braking resistor and braking chopper are working 

correctly.

• Check motor parameter settings and adjust torque and slip compensation, 

AFR and hunting prevention as needed.

• Make sure that the power supply voltage meets the drives specifications.

to

to

or

Summary of Contents for CIMR-VC*****H**-00 series

Page 1: ...O TOEP C710606 75B Type CIMR VC H 00 Models 200 V Class Single Phase Input 0 1 to 3 0 kW 400 V Class Three Phase Input 0 2 to 18 5 kW To properly use the product read this manual thoroughly and retain...

Page 2: ...n permission of Yaskawa No patent liability is assumed with respect to the use of the information contained herein Moreover because Yaskawa is constantly striving to improve its high quality products...

Page 3: ...00 IP66 Quick Start Guide Table of Contents 1 GENERAL INFORMATION AND SAFETY INSTRUCTIONS 4 2 MECHANICAL INSTALLATION 8 3 ELECTRICAL INSTALLATION 13 4 KEYPAD OPERATION 17 5 START UP 19 6 PARAMETER TAB...

Page 4: ...eries IP66 Type drives Receiving Please perform the following tasks after receiving the drive Inspect the drive for damage If the drive appears damaged upon receipt contact your supplier Verify receip...

Page 5: ...ious injury YASKAWA is not responsible for any modification of the product made by the user This product must not be modified Never submerge this product in water Using this product in water can damag...

Page 6: ...ding to IEC 60755 Sudden Movement Hazard Stay clear of the motor during rotational Auto Tuning The motor may start operating suddenly During automatic starting of equipment the machine may start movin...

Page 7: ...issing parts Prevent moisture and other solvents from entering the drive enclosure Failing to do so can damage the drive or considerably shorten its expected performance life Install adequate branch c...

Page 8: ...od possible with other models Environment Conditions Installation Area Indoors Ambient Temperature 10 C to 40 C Drive reliability improves in environments without wide temperature fluctuations Storage...

Page 9: ...efore the front cover can be removed NOTICE Never disassemble the protective case that encloses the drive The case is constructed as a single continuous piece that includes the heatsink Attempting to...

Page 10: ...drive NOTICE RJ45 connector on drives with model code CIMR 0081 is meant to connect an external digital operator JVOP 180 LCD JVOP 182 LED with recommended cable YASKAWA part No 72606 WV003 or JVOP 1...

Page 11: ...utside may allow water or oil into the drive and damage components Cable Glands Specifications and Model Numbers YASKAWA recommends using SKINTOP cable glands by Lapp Kabel for use with V1000 Series I...

Page 12: ...Wiring glands are plastic Part No Model PG Size Wrench Size SW mm A mm B mm C mm D mm Body 53015140 STR 16 16 27 44 10 53015040 ST 16 Locknut 53019040 GMP GL 16 16 30 33 6 Part No Model PG Size Wrench...

Page 13: ...d 2 Multi function digital inputs default setting Link Thermal relay Braking resistor opt V1000 IP66 Ground Multi function relay output 250 Vac 30 Vdc 10 mA to 1A default setting Fault During run Freq...

Page 14: ...switch with a large capacity power supply transformer over 600 kVA Wiring the Main Circuit Output Consider the following precautions for the output circuit wiring Do not connect any other load than a...

Page 15: ...e CIMR 0080 can be connected to PC by using JVOP 181 USB Copy Unit Use the RJ45 connector where the Digital Operator is connected Ground the cable shields with the maximum contact area of the shield a...

Page 16: ...rive output disabled time from input open to drive output switch off is less than 1 ms Both Closed Normal operation H2 Drive Disable Input 2 Multi Function Relay Output MA N O fault Digital relay outp...

Page 17: ...e LOCAL mode The Stop LED is on when the drive is not operating the motor flashes during deceleration at a fast stop or stop by interlock operation is off during run deceleration to stop or when the f...

Page 18: ...urrent Output Voltage Monitor Display Verify Menu Setup Mode Parameter Setting Mode Auto Tuning DRV LED is on A Run command will start the motor The Monitor Displays are used to read out drive data li...

Page 19: ...arameter settings are unknown Open Loop Vector Control OLV A1 02 2 General variable speed applications Applications requiring high precision high speed control PM Open Loop Vector Control A1 02 5 Dera...

Page 20: ...ility OL2 150 of drive rated current for 60 s 120 of drive rated current for 60 s L3 02 Stall Prevention during Acceleration 150 120 L3 06 Stall Prevention during Run 150 120 Default carrier frequency...

Page 21: ...n of each analog input can be assigned in the H3 parameters The default setting of both inputs is Frequency bias Input A1 is set for 0 to 10V input and A2 is set for 4 20 mA input The addition of both...

Page 22: ...to 0 00 seconds Acceleration Deceleration C1 01 Accel Time 1 Sets the acceleration time 1 from 0 to the max output frequency C1 02 Decel Time 1 Sets the deceleration time 1 from the max output frequen...

Page 23: ...blower cooled motor 3 Vector motor L1 02 Motor Overload Prot Time Sets the motor overload protection time in min Normally no change is necessary Stall Prevention L3 01 Stall Prevention Selection durin...

Page 24: ...at occurred through the fourth most recent fault U3 05 to U3 08 Accumulated operation time at the most recent fault through the fourth most recent fault U3 09 to U3 14 Lists the fifth most recent faul...

Page 25: ...Replace any broken parts Reduce the carrier frequency Drive Disable Both Drive Disable inputs are open The drive output is safely disabled and the motor can not be started Check why the upper control...

Page 26: ...tting range Set parameters to the proper values oPE03 A contradictory setting is assigned to multi function contact inputs H1 01 through to H1 06 The same function is assigned to two inputs this exclu...

Page 27: ...he acceleration time C1 01 If possible disconnect the load Er 12 Current detection error One or all output phases are lost Current is either too low or exceeds the drives rating The current sensors ar...

Page 28: ...nt Cover on page 9 3 Make sure the charge LED on the drive has gone off 4 Unplug the internal fan cable connector 3 wires right side connector from the drive 5 Unmount the stirring fan holding bracket...

Page 29: ...apacitors to discharge 2 Remove the IP66 front cover as described in Removing the Front Cover on page 9 3 Make sure the charge LED on the drive has gone off 4 Unplug the external fan cable connector 2...

Page 30: ...8 Maintenance EN 30 YASKAWA Europe TOEP C710606 75B AC Drive V1000 IP66 Quick Start Guide...

Page 31: ...re given on the bottom of the back cover Date of Publication Rev No Section Revised Contents October 2010 First Edition June 2013 2 Front Back Covers Content Pages Cover Revision including Logo Update...

Page 32: ...ct to change without notice for ongoing product modifications and improvements 2013 YASKAWA EUROPE GmbH All rights reserved EUROPEAN HEADQUARTERS YASKAWA EUROPE GmbH Hauptstra e 185 65760 Eschborn Ger...

Reviews: