User Constants
8.2.4 Motor Constant Constants: E
- 16
J
Motor 2 Setup: E5
Constant
Name
Setting
Factory
Change
during
Control Methods
Constant
Number
Display
Description
Setting
Range
Factory
Setting
g
during
Opera-
tion
Open Loop
Vector
Flux Vector
Page
E5-01
Motor 2 rated current
Sets the motor rated current in 1 A
units.
These set values will become the
reference values for motor
0.32 to
6.40
1.90
A
6
E5-01
Motor 2 rated FLA
reference values for motor
protection, torque limits.
These values will automatically
be set if they were set during au-
totuning.
6.40
*2
1.90
*1
A
- 6
E5-02
Motor 2 rated slip
Sets the motor rated slip in Hz
units.
These set values will become the
f
l
f
li
0.00 to
2.90
A
6
E5-02
Motor 2 Slip Freq
reference values for slip com-
pensation.
These values will be automati-
cally set during autotuning.
0.00 to
20.00
2.90
*1
A
- 6
E5-03
Motor 2 no-load cur-
rent
Sets the motor no-load current in 1
A units.
Th s
l
s
ill b
tom tic l
0.00 to
1500 0
1.20
*1
A
- 7
E5 03
Motor 2 No-load 1
These values will be automatical-
ly set during autotuning.
1500.0
*1
A
- 7
E5-04
Motor 2 number of
poles
Sets the number of motor poles.
These values will automatically
2 to 48
4
E5 04
Motor 2 # Poles
These values will automatically
be set during autotuning.
2 to 48
4
E5-05
Motor 2 line-to-line
resistance
Sets the motor phase-to-phase re-
sistance in
:
units.
Th s
l
s
ill b
tom tic l
0.000 to
65 000
9.842
*1
A
- 7
E5 05
Motor 2 term Ohms
These values will be automatical-
ly set during autotuning.
65.000
*1
A
- 7
E5-06
Motor 2 leak induc-
tance
Sets the voltage drop due to motor
leakage inductance as a percentage
of the motor rated voltage.
0.0 to
30 0
18.2
*1
A
- 7
E5 06
Motor 2 Leak
of the motor rated voltage.
These values will be automatical-
ly set during autotuning.
30.0
*1
A
- 7
* 1. The factory setting depends upon the Inverter capacity. The values for a 200 V class Inverter of 0.4 kW are given. See page
- 35.
* 2. The setting range is 10% to 200% of the Inverter’s rated output current. The value for a 200 V class Inverter of 0.4 kW is given.
8