8.1
Initialize Mode Constants
- 3
8.1
Initialize Mode Constants
Constant
Name
Setting
Factory
Change
during
Control Methods
Constant
Number
Display
Description
Setting
Range
Factory
Setting
g
during
Opera-
tion
Open Loop
Vector
Flux Vector
Page
A1-00
Language selection
for digital operator
display
Used to select the language dis-
played on the Digital Operator
0: English
1: Japanese
0 1
1
Q
Q
- 19
Select Language
1: Japanese
This constant is not initialized by
the initialize operation.
A1-01
Constant access level
Used to set the constant access lev-
el (set/read.)
0: Monitoring only (Displays only
Operation mode and Initialize
mode)
1: Used to select user constant
0 to 4
2
Q
Q
19
A1-01
Access Level
1: Used to select user constant
(Constants A2-01 to A2-32 only
can be set/read.)
2: Quick-Start :
Q
3: Basic :
B
4: Basic :
A
0 to 4
2
Q
Q
- 19
A1-02
User setting constant
Used to select the control method
for the Inverter
2: Open loop vector
2 3
2
Q
Q
20
A1-02
User Param 1 to 32
2: Open loop vector
3: Flux vector
This constant is not initialized by
the initialize operation.
2 3
2
Q
Q
- 20
A1-03
Initialize
Used to initialize the constants us-
ing the specified method.
0: No initializing
1110: Initializes using the User
constants
0 to
0
Q
Q
21
A1-03
Init Constants
constants
2220: Initializes using a two-wire
sequence. (Initializes to the
factory setting.)
3330: Initializes using a three-wire
sequence.
0 to
3330
0
Q
Q
- 21
A1-04
Password 1
Password input when a password
has been set in A1-05. This func-
tion write-protects some constants
of the Initialize mode.
If the password is changed A1 01
0 to
0
Q
Q
23
A1-04
Enter Password
If the password is changed, A1-01
to A1-03 and A2-01 to A2-32
constants can no longer be
changed. (Programming mode
constants can be changed.)
0 to
9999
0
Q
Q
- 23
A1-05
Password 2
Used to set a four digit number as
the password.
This constant is not usually dis-
played. When the password
0 to
0
Q
Q
23
A1-05
Select Password
played. When the password
(A1-04) is displayed, hold down
the Reset/Select Key and press
the Menu Key and the password
will be displayed.
0 to
9999
0
Q
Q
- 23
A2-01 to
User setting constant
Used to set the constant numbers
that can be set/read. Maximum 32.
Effective when the access level
(A1 01) i
t t U
P
b1-01
to
A
A
23
A2 01 to
A2-32
User Param 1 to 32
(A1-01) is set to User Program
(1). Constants set in constants
A2-01 to A2-32 can be set/read
in the Programming mode.
to
o2-08
----
A
A
- 23
8