2 Mechanical Installation
YASKAWA Europe
TOEP C710606 96A - AC Drive A1000 IP54 Wallmount - Quick Start Guide
EN 11
Wiring Instructions
WARNING!
Never open the panel door while the power is on. Failing to do so may result in serious electric shock.
1.
Open the drive with panel key. Optional mains switch has to be in OFF-position to open the panel door.
2.
Install recommended cable glands for main circuit and control wiring.
Note:
Before wiring up the drive, remove the sealing grommets from the access holes in the bottom of the drive. The figure below
explains the purpose of each hole. Make sure the proper holes are used. Do not remove the sealing grommets from holes that will
not be used.
3.
Route the cables through the assigned gland and connect power supply and motor cable as shown below.
Example drawing shows A1000 IP54 drive with optional mains switch.
Cable Glands
Control Circuit Wiring
Note:
Main circuit wires should be multi-conductor shielded line with a continuous maximum allowable temperature of over 70
C
(such as ÖLFLEX® CLASSIC 110/115CY and UNITRONIC® LiYCY (TP) by Lapp Kabel).
Drive Side Wiring Hole
<1> Sealing grommets are fitted to control circuit wiring holes on receipt.
<2> Note that the cable gland body and locknut are sold separately.
Recommended Cable Glands for Control (Wiska)
Diameter (mm)
Number of Holes
Cable Diameter (mm)
23
2
SKV16 / MUG 16
8 to 14
open with panel key
Drives with optional
mains switch:
turn to OFF-position to open
Air Intake
Air Intake
Control wiring
Control wiring
Motor cable
Motor cable
Power supply cable
Power supply cable
L1 L2 L3
Drives without mains switch:
Please connect power supply cable directly to
L1/2/L3 terminals of the EMC filter. Connect
the earth wire to earth terminal of the
EMC filter. Use ferrules for L1/L2/L3 wires.
Drives with built-in mains switch:
Please connect power supply cable directly to
L1/2/L3 terminals of the mains switch.
Use ferrules for L1/L2/L3 wires.
Earth connection
motor cable
Motor cable connection
For all drives:
Earth connection of the power supply
directly to the earth terminal of the
EMC filter.
Use ring cable terminal for earth cable.
L1 L2 L3
L1 L2 L3