3 Electrical Installation
EN 14
YASKAWA Europe TOEP C710606 96A - AC Drive A1000 IP54 Wallmount - Quick Start Guide
Wiring Specification
Main Circuit
Mains Connection
Use the fuses listed in the table below when wiring the main circuit and connect L1, L2, L3 as specified in drawing
Electrical Installation on page 13
Motor Connection
Control Circuit
The control terminal board is equipped with screwless terminals. Always use wires within the specification listed below.
Model
CIMR-A
<1> Use ferrules for flexible wire power supply cable
<2> Use ring cable terminals for earth cable connection at the EMC filter. Connect earth power supply earth directly to EMC filter earth terminal.
Mains Fuse
[Bussmann]
Applicable
cable (mm
2
)
Recommended
cable (mm
2
)
Ferrule Length
(mm, max.)
Screw Size / Tightening Torque (Nm)
4A0044
FWH-250A
16 to 25
16
15
M5 slotted
2 to 4 Nm
M8
9 to 11 Nm
4A0058
4A0072
16 to 50
M6 slotted
2.5 to 5 Nm
4A0088
25
25
M6
3 to 6 Nm
M10
18 to 23 Nm
4A0103
25 to 50
35
4A0139
FWH-350A
35 to 95
50
M8
6 to 12 Nm
4A0165
FWH-400
50 to 95
70
4A0044-0095
FWH-250A
16 to 25
16
10
M6
4 Nm
M8
9 to 11 Nm
4A0058-0095
4A0072-0095
16 to 50
4A0088-0095
50 to 95
50
15
M10
22.6 Nm
M10
18 to 23 Nm
4A0103-0095
4A0139-0095
FWH-350
4A0165-0095
FWH-400
70
Model
CIMR-A
(all types)
<1> Use ring cable terminals.
Applicable cable
(mm
2
)
Recommended
cable (mm
2
)
Drive Terminals
Screw Size / Tightening Torque (Nm)
U/T1,V/T2,W/T3,
– , +1, +2
+3
B1, B2
4A0044
2.5 to 25
16
M6
4 to 6 Nm
–
M5
2 to 2.5 Nm
M8
9 to 11 Nm
4A0058
M8
9 to 11 Nm
M8
9 to 11 Nm
4A0072
2.5 to 50
25
4A0088
16 to 50
M10 18 to 23 Nm
–
M10 18 to 23 Nm
4A0103
35
4A0139
25 to 95
50
M10 18 to 23 Nm
4A0165
70
Wire Type
Wire size (mm
2
)
Ferrule Length (mm)
Solid
0.2 to 1.5
-
Flexible
0.2 to 1.0
-
Flexible with ferrule (recommended)
0.25 to 0.5
8