3 Electrical Installation
EN 18
YASKAWA Europe TOEP C710606 96A - AC Drive A1000 IP54 Wallmount - Quick Start Guide
NOTICE:
The terminals HC, H1, H2 are used for the Safe Disable function. Do not remove the wire link between HC, H1, or H2 unless
the Safe Disable function is used.
Refer to Safe Disable Input Function on page 35
NOTICE:
The wiring length to the terminals HC, H1 and H2 should not exceed 30 m.
Internal Cooling Fan
To ensure proper air circulation inside the IP54 enclosure A1000 IP54 drives have a built-in circulation fan. This fan is
monitored for proper operation by wiring to S3 digital input of the drive. If the fan does not work correctly the drive
stops operation and shows an “EF3” message on the digital operator.
When the A1000 IP54 is operated with control signals other than default (Sink Mode, internal power supply), the fan
monitor wiring has to be changed accordingly to following table.
After changing Sink/Source configuration the digital operator should not show “EF3”, otherwise fan monitoring is not
wired correctly. An “EF3” fault cannot be reset until fan monitor wiring is corrected (according to the table below).
Monitor Output
MP
Pulse train output (Output frequency)
32 kHz (max)
FM
Analog monitor output 1 (Output frequency)
-10 to +10 Vdc, 0 to +10 Vdc, or 4 to 20 mA
Use jumper S5 on the control terminal board to select between voltage
or current output at terminals AM and FM. Set parameters H4-07 and
H4-08 accordingly when changing the jumper setting.
AM
Analog monitor output 2 (Output current)
AC
Monitor common
0 V
DM+ Safety monitor output
Outputs status of Safe Disable function. Closed when both Safe
Disable channels are closed. Up to +48 Vdc 50 mA
DM-
Safety monitor output common
Drive Internal Power Supply (SN and SP)
External 24Vdc Power Supply
Sinking Mode (NPN)
Sourcing Mode (PNP)
Type
No.
Terminal Name (Function)
Function (Signal Level) Default Setting
Default wiring fan monitor:
(Internal sink Mode, npn)
Red wire: S3, Black wire: SN
S3
SN
Black wire
Red wire
( Default )
SC
S3
24 Vdc
SP
SN
SC
S3
24 Vdc
SP
SN
External
24 Vdc
Black wire
Red wire
Black wire
Red wire
SC
S3
24 Vdc
SP
SN
SC
S3
24 Vdc
SP
SN
External
24 Vdc
Black wire
Red wire