8 CC-Link Data Table
32
YASKAWA ELECTRIC
SIEP C730600 83D YASKAWA AC Drive Option SI-C3 Technical Manual
Note: 1.
If making frequent setting changes, use RYD (Frequency Reference 1 flag) for setting the register. You can write data to the
EEPROM used for the drive 100,000 times. Do not use this write command frequently.
2.
Although RYE and RYF are triggered by the rising edge of the signal, they are otherwise enabled depending on the value that is input.
Drive
→
PLC
Table 14 Remote I/O Table (Drive
→
PLC)
RY15
Terminal S2 Function
Multi-function input: H1-02
Function is disabled when
for the Reverse Run
Command (H1-02 = 41).
RY16 to 19
Reserved
–
–
RY1A
Fault Reset
Resets a drive fault
–
RY1B to 1F
Reserved
–
–
Device
<1> Terminals will differ depending on the model of the drive. Refer to
Terminals that Change depending on the Model of the Drive on page 37
for information on terminals.
Signal Name
Description
Default
RX0
Forward Run
ON: Forward Run Command Present (includes DC Injection Braking)
OFF: No Forward Run Command
–
RX1
Reverse Run
ON: Reverse Run Command Present
OFF: No Reverse Run Command (includes DC Injection Braking)
–
RX2
YASKAWA AC Drive
1000-Series: Terminals M1,
M2 Function
YASKAWA AC Drive
GA700, GA800:
Multi-function digital output
1 Function
GA500:Terminals MA/
MB-MC Function
Multi-function output: H2-01
YASKAWA AC Drive
1000-Series, GA700,
GA800:
H2-01 = 0: During Run
GA500: H2-01 = E: Fault
RX3
Speed Agree
ON: Output frequency is between frequency reference and the detection
width set to L4-02.
–
RX4
During Stall Prevention
–
–
RX5
During Undervoltage
–
–
RX6
YASKAWA AC Drive
1000-Series, GA500:
Terminal P1 Function
YASKAWA AC Drive
GA700, GA800:
Multi-function digital output
2 Function
Multi-function output: H2-02
YASKAWA AC Drive
1000-Series, GA700,
GA800: H2-02 = 1: Zero
Speed
GA500: H2-02 = 0:
During Run
RX7
YASKAWA AC Drive
1000-Series, GA500:
Terminal P2 Function
YASKAWA AC Drive
GA700, GA800:
Multi-function digital output
3 Function
Multi-function output: H2-03
H2-03 = 2: Speed Agree 1
RX8, 9
Reserved
–
–
RXA
CC-Link Option Fault
Communication error between drive and CC-Link device
–
RXB
Monitoring Motor
Revolutions
ON: Currently monitoring motor revolutions.
Data is stored in remote
register RW
R1
.
RXC
Obtain Monitor Data
ON: Monitor data has been updated.
–
RXD
Frequency Setting Ready 1
ON: Displays the main frequency reference that has been set.
–
RXE
Frequency Setting Ready 2
ON: Displays the data set to d1-01 (Frequency Reference 1).
Note:
Also sets the main frequency reference at the same time.
–
RXF
Command Code Execute
Complete
ON: Displayed after the specified command code has been executed.
RXF signal switches off when the RYF command is no longer present.
–
RX10 to 19
Reserved
–
–
RX1A
Error
ON: Fault occurred on the drive side.
–
RX1B
Remote Station Ready
ON: Drive is ready to operate.
–
RX1C to 1F
Reserved
–
–
Signal
Name
Description
Default