5 Installation Procedure
22
YASKAWA ELECTRIC
SIEP C730600 83D YASKAWA AC Drive Option SI-C3 Technical Manual
Option Connection Diagram
Figure 21
Figure 21 Using a single drive
Figure 22
Figure 22 Using multiple drives
<1> The option must be configured with a termination resistor. For instructions, refer to
Termination Resistor Connection on page 23
<2> Make sure that the FG terminal on the master drive is grounded properly.
<3> Connect the provided ground wire for installations on 1000-series drives and GA500 drives.
The ground wire is not necessary for installation on GA700 or GA800 drives.
<1> The option must be configured with a termination resistor. For instructions, refer to
Termination Resistor Connection on page 23
<2> Make sure that the FG terminal on the master drive is grounded properly.
<3> Connect the provided ground wire for installations on 1000-series drives and GA500 drives.
The ground wire is not necessary for installation on GA700 or GA800 drives.
CC-Link
Option
DA
DB
DG
SLD
SLD
DA
DB
DG
SLD
FG
Master
device
CC-Link cable
Drive
Termination resistor
<1>
FE
<3>
<2>
CC-Link
Option
DA
DB
DG
SLD
SLD
CC-Link
Option
DA
DB
DG
SLD
SLD
DA
DB
DG
SLD
FG
CC-Link
Option
DA
DB
DG
SLD
SLD
Master
device
Drive
Drive
Drive
CC-Link cable
Termination resistor
<1>
FE
<3>
FE
<3>
FE
<3>
<2>