Energy-Saving Unit Extended Command Codes
Table 34 Energy-Saving Unit Extended Command Codes
Command Code
Name
Read
Write
BIT
100H
–
Operation signals
0
/Automatic Run Command, Stop Command
1
Forced Run command, Stop Command
2
External fault (EF0)
3
Fault reset
4
Multi-function input 1
5
Multi-function input 2
6
Multi-function input 3
7
Multi-function input 4
8
Multi-function input 5
9
Multi-function input 6
A
Multi-function input 7
B
Multi-function input 8
C to F
Reserved
105H
205H
Multi-function analog monitor output terminal 1
106H
206H
Multi-function analog monitor output terminal 2
107H
–
Multi-function relay output
0
Multi-Function Contact Outputs (terminal M1-M2) 1: ON 0: OFF
1
Multi-Function Photocoupler Output 1 (terminal P1-PC)
1: ON 0: OFF
2
Multi-Function Photocoupler Output 2 (terminal P2-PC)
1: ON 0: OFF
3-5
Reserved
6
1 : Bit 7 function enabled
7
1 : Fault Contact Output (terminal MA/MB-MC) 1
:
ON
0
:
OFF
8-F
Reserved
110H
–
Status signal
0
1: During Run 0: During Stop
1
Reserved
2
1: During Regenerative Operation
3
1: During Reset Signal Input
4
1: During run (Operation Ready)
5
1: Operation Ready
6
1: Alarm
7
1: Fault
8
1: oPE Error
9
1: Momentary Power Loss Ridethru 0: Recovery from Momentary Power Loss
A
1: ComCtrl status/NetCtrl status
B, C
Reserved
D
1: During Active Current Limit
E, F
Reserved
117H
–
Analog input terminal A1
11CH
–
Analog input terminal A2
11EH
–
Analog input terminal A3
120H
–
Fault contents 1
121H
–
Fault contents 2
122H
–
Fault contents 3
123H
–
Fault contents 4
124H
–
Fault contents 5
125H
–
Fault contents 6
126H
–
Fault contents 7
130H
–
131H
–