Option7: TMO (Low-Byte)
Range of values: 0 ... 65535
n
Default: 250
You may select 1 or 2 start identifications. When you select "1" as number of start identifi-
cations, the contents of the 2. start identification is ignored.
Range of values: 0 ... 2
n
Default: 1
The ASCII value of the start character that precedes a telegram to signify the start of a
data transfer. You may select 1 or 2 start characters. When you are using 2 start charac-
ters you have to specify "2" at
Number start identifications.
Start identification 1, 2: Range: 0 ... 255
n
Start identification 1: Default: 3
n
Start identification 2: Default: 0
You may select 1 or 2 end identifications. When you select "1" as number of end identifi-
cations, the contents of the 2. end identification is ignored.
Range of values: 0 ... 2
n
Default: 1
The ASCII value of the end character that precedes a telegram to signify the end of a
data transfer. You may select 1 or 2 end characters. When you are using 2 end charac-
ters you have to specify "2" at
Number end identifications
.
End identification 1, 2: Range: 0 ... 255
n
End identification 1: Default: 3
n
End identification 2: Default: 0
Via the Operating mode you may specify if the interface is operated in half-duplex
(RS485) or full-duplex (RS422) operation.
At half-duplex parameterization with RS485 software data flow control is
not possible.
Value
Description
00h
Half-duplex - Two-wire operation (RS485)
Data is exchanged between the communication partners but only in one direction at a time. In half-
duplex operation, therefore, at any one time data is being either sent or received.
01h
Full-duplex - Four-wire operation (RS422)
Data is exchanged between the communication partners in both directions simultaneously. In full-
duplex operation, therefore, data may be sent and received at the same time. Each communication
partner must operate simultaneously a receipt line.
Range of values:
OPTION8: Number start
identifications
OPTION9: 10: Start identi-
fications 1, 2
OPTION11: Number end
identifications
OPTION12, 13: End identi-
fications 1, 2
OPTION15: Operating
mode
VIPA System SLIO
Serial communication protocols
STX/ETX > Parameter data of STX/ETX
HB300 | CP | 040-1CA00 | en | 18-28