With a bus coupler bus interface and power module is integrated to one casing. With the
bus interface you get access to a subordinated bus system. As head module, via the inte-
grated power module for power supply, bus interface and the electronic of the connected
periphery modules are supplied. The DC 24 power section supply for the linked periphery
modules is established via a further connection of the power module. By installing of up to
64 periphery modules at the bus coupler, these are electrically connected, this means
these are assigned to the backplane bus, the electronic modules are power supplied and
each periphery module is connected to the DC 24V power section supply.
CAUTION!
Bus interface and power module may not be separated!
Here you may only exchange the electronic module!
In the System SLIO there is the possibility to place up to 64 modules in on line. By means
of the line extension you can divide this line into several lines. Here you have to place a
line extension master at each end of a line and the subsequent line has to start with a line
extension slave. Master and slave are to be connected via a special connecting cable. In
this way, you can divide a line on up to 5 lines. For each line extension the maximum
number of pluggable modules at the System SLIO bus is decreased by 1. To use the line
extension no special configuration is required.
Each periphery module consists of a
terminal
and an
electronic module
.
1
Terminal module
2
Electronic module
Bus coupler
Line extension
Periphery modules
VIPA System SLIO
Basics and mounting
System conception > Components
HB300 | CP | 040-1CA00 | en | 18-28
11