4.5 Diagnostic data
Via the parameterization you may activate a diagnostic interrupt for the module. With a
diagnostic interrupt the module serves for diagnostic data for diagnostic interrupt
incoming
.
As soon as the reason for releasing a diagnostic interrupt is no longer present, the diag-
nostic interrupt
going
automatically takes place.
Within this time window (1. diagnostic interrupt
incoming
until last diagnostic interrupt
going
) the
MF-LED of the module is on.
DS - Record set for access via CPU, PROFIBUS and PROFINET. The access happens
by DS 01h. Additionally the first 4 bytes may be accessed by DS 00h.
IX - Index for access via CANopen. The access happens by IX 2F01h. Additionally the
first 4 bytes may be accessed by IX 2F00h.
SX - Subindex for access via EtherCAT with Index 5005h.
More can be found in the according manual of your bus coupler.
Name
Bytes
Function
Default
DS
IX
SX
ERR_A
1
Diagnostic
00h
01h
2F01h
02h
MODTYP
1
Module information
1Ch
03h
ERR_C
1
reserved
00h
04h
ERR_D
1
Diagnostic
00h
05h
CHTYP
1
Channel type
60h
06h
NUMBIT
1
Number diagnostic bits per channel 08h
07h
NUMCH
1
Number channels of the module
01h
08h
CHERR
1
Channel error
01h
09h
CH0ERR
1
Channel-specific error
01h
0Ah
CH1ERR...CH
7ERR
7
reserved
00h
0Bh ... 11h
DIAG_US
4
µs ticker
00h
13h
Byte
Bit 7 ... 0
0
n
Bit 0: set at module failure
n
Bit 1: set at internal error
n
Bit 2: set at external error
(wire break possible only with RS422 )
n
Bit 3: reserved
n
Bit 4: set at missing external power supply
n
Bit 5, 6: reserved
n
Bit 7: set at error in parameterization
Overview
ERR_A Diagnostic
VIPA System SLIO
Deployment
Diagnostic data
HB300 | CP | 040-1CA00 | en | 18-28
54