2
Installation and wiring
2-27
CC-Link
n
5 4 3 2 1
Terminal arrangement and connector specifications
No.
Name
1
DA
2
DB
3
DG
4
NC
5
SLD
23212-M0-00
TS-X, TS-P
TS-S, TS-S2,
TS-SH
Connection method
CC-Link connector
Jump socket
23213-M0-00
Manufacturer part name
Manufacturer name
CC-LINK connector
35505-6000-B0M GF
3M Japan Corporation
Jump socket
35715-L010-B00 AK
3M Japan Corporation
Wiring method
Insert the cable all the way into
the connector, and view from the
top cover to verify that the wires
are fully inserted (to the position
of the dotted line).
Position the pliers from the side of
the connector, and press the
cover onto the body to clamp the
connector onto the cable.
Verify that the cover is level with
the body, and that there is no gap
between the body and the cover.
* We recommend that you use heat-shrink tubing to protect the drain wire and the other wires.
23220-M0-00
n
NOTE
The CC-Link unit supports CC-Link Ver.1.10. The use of Ver.1.10 compatible CC-Link cable eliminates some
restrictions which apply to items such as the cable length between nodes, etc. For details, refer to the instruction
manual for the Ver.1.10 compatible master station PLC.