15
command (only valid for main frequency
P00.00, speed reduction step is specified
by parameter P00.20)
12: External terminal speed reduction
command (only valid for main frequency
P00-00, speed reduction step is specified
by parameter P00-20)
13: External fault normally open input,
"external fault" is generated at the moment
of closing action
14: External fault normally closed input,
"external fault" is generated at the moment
of disconnection
15: External fault, closing produces
"external fault"
16: External fault, disconnection produces
"external fault"
17: Used as external fault reset input
P00.18
Multi-function input X2
function selection
1
P00.19
Multi-function input X3
function selection
0
P00.20
Multi-function input X4
function selection
0
P00.21
External terminal up/down
speed increment
0.0-600.0HZ
1.0HZ
P00.22
Time interval of external
terminal up/down
2
P00.23
Physical quantity display
proportional constant
0-999.9%
100.00%
P00.24
Display item selection after
power-on
0: Display the current target frequency
1: Display motor operating frequency
2: Display motor running current
3: Display the current input AC voltage
4: Display the current bus voltage
5: Display the current output voltage
6: Display the current speed segment
number SP x
7: Display the internal temperature of the
inverter t xx
8: Display input signal X1-X3/output
signal
9: Display user variables, namely: current
output frequency X P00.23
10: Display user count value
11: Display manufacturer's temporary
0