N°
Parameter
Description
module overtemper-
ature alarm has
been triggered
A7
SHORT CIRC
Total number of
times the motor
short circuit alarm
has been triggered.
A8
OVER VOLT
Total number of
times the overvolt-
age on converter
power supply line
alarm has been trig-
gered.
A9
UNDER VOLT
Total number of
times the undervolt-
age on converter
power supply line
alarm has been trig-
gered.
5.3 Programming
The converter has two parameter menus that are ac-
cessed with a combination of keys:
• MB, BASIC MENU
• ME, ADVANCED MENU
NOTICE:
• The converter is delivered already programmed
with the default values. Edit the values according
to the type of electric pump and system.
• If the converter is already fitted with an electric
pump, it has been programmed in relation to the
characteristics of the electric pump. Edit the func-
tion values of the system.
• Incorrect configuration can damage the electric
pump and/or the system.
5.3.1 BASIC MENU (MB) parameters
In MANUAL mode and with the LED (10) off:
1. Press and hold (3) to access the parameters
(MB). The LED (10) flashes.
2. Press (4) and (5) to edit the value of the param-
eter.
3. Press (6) to confirm and move on to the next
parameter.
4. Press (3) or (6) in sequence to exit the menu.
The LED (10) turns off.
Table 17: Models MMW and MTW
Pa-
ram-
eter
Description
Range
Unit of
meas-
urement
Default
A
Set the current
rating value of
the motor on
the data plate.
0.1 to
9.0
(MMW)
0.1 to
10.0
(MTW)
Ampere Imax(*)
Pa-
ram-
eter
Description
Range
Unit of
meas-
urement
Default
FL
Minimum start-
up and stop
frequency of
the motor. Fre-
quency at
which the con-
verter begins to
run (upon start-
up and shut-
down) without
using the
ramps.
30 to 48
(MMW)
15 to 48
(MTW)
Hz
30
EL
Enable the digi-
tal input and
connect the
level sensor to
ensure that the
pump stops
when there is
no water. Refer
Alarm
A1
if pa-
rameter
EL
=1
and the electri-
cal contact is
open.
0: Disa-
bled, no
control
1: Ena-
bled
-
0
SP
Set the re-
quired pressure
value of the
system (set
point)
0.5 to
8.0
bar
2.5
MP
Pressure value
of the system
below which
the
A4
"mini-
mum pressure"
alarm is trig-
gered. When
the alarm is
triggered, the
pump stops
and the ART
function is ena-
bled. See
.
Triggering of
the alarm is de-
layed by the
amount of time
set in the
dL
parameter.
0.0 to
(
SET
PRESS
-0.4)
0.0: Dis-
abled
bar
0
dL
Delay timer for
triggering the
"minimum pres-
sure" alarm
(
MP
parame-
ter).
0 to 99
sec
20
rS
For three-
phase motors,
invert the direc-
tion of rotation.
0 to 1
-
0
10
lmax: maximum current supplied. The value varies according to the model of converter.
en - Original instructions
34
Summary of Contents for Lowara ResiBoost MMA Series
Page 197: ...N 254 V 2 5 DC Bus N A9 T MMW MTW MMA MTA 184 V 7 7 1 MMW MTW MMA MTA A 30m EL SP el 197...
Page 200: ...30 mA RCD B 9 9 1 LED el 200...
Page 229: ...15 4 20mA QCL5 Max Min Max Min G WH BN inst m_03 SC BP it en fr de es pt nl pl el tr 229...
Page 234: ...22 INST G_11_B SC 7 6 5 4 3 2 1 13 8 11 12 2 10 11 2 14 15 it en fr de es pt nl pl el tr 234...
Page 235: ...23 INST G_12_B SC 1 2 7 15 14 6 5 4 3 8 9 2 10 11 12 18 13 it en fr de es pt nl pl el tr 235...
Page 236: ...24 INST G_13_B SC 2 1 13 8 11 12 2 10 11 2 14 15 16 11 17 it en fr de es pt nl pl el tr 236...
Page 237: ...25 13 15 14 INST G_14_B SC 8 9 2 1 2 10 11 12 18 17 16 11 it en fr de es pt nl pl el tr 237...
Page 243: ......