For models MMA and
MTA, see
1. Unfasten the 8
screws and open the
FRONT cable mak-
ing sure not to dam-
age the connecting
cable of the display
and the connector.
2. Insert the cable of
the pressure sensor
in the relative cable
gland, see
if the cable is miss-
ing or needs to be
replaced.
3. If required, connect
the cable of the level
sensor to the digital
input to prevent dry
running of the pump.
The electrical con-
tact must be normal-
ly open when an
alarm is triggered,
. Suit-
able cable 2 x (0.75
to 1.5) mm
2
. Check
that all the cables
are secured, includ-
ing the connecting
cable of the display,
and close the
FRONT cover and
fasten the 8 screws.
4.4.3 Analogue pressure sensor
An analogue sensor with 4-20mA output is required
to monitor the pressure in the system constantly.
Converter models MMA and MTA require an external
sensor. See
power cable and a 0-16bar sensor are provided as
standard.
The pressure sensor for models MMW and MTW is
inside the converter.
Be sure the following are adhered to:
• Use cables resistant to heat up to +70°C (158°F)
for all the connections.
• The wires that are connected to the power termi-
nals, the pressure sensor (MMA, MTA), and the
contact for protection against dry running must
be separate and have reinforced insulation.
• Be careful not to drop bits of wire or sheathing or
other foreign materials into the converter when
making the electrical connections. Take all due
care to avoid damaging the internal parts when
removing anything inside.
4.4.4 Applications with very long cables
If the cable between the converter and the motor is
more than 30 meters in length, it is ADVISABLE to
install a dV/dt or sinusoidal filter.
The filters extend the life-span of the insulation and
reduce the noise of the motor.
Inductance on the side of the motor (dV/dt filter) re-
duces the dv/dt at the rising edge and the phases,
leveling the waveform of the current.
The sinusoidal filter makes both the waveform of the
current and the waveform of the voltage at the out-
put of the frequency converters sinusoidal.
Be sure that the following are adhered to:
and
.
• Install the filter between the converter and the
motor.
• Install the filter as near as possible to the output
of the converter, at a max distance of L1max.
• IP64 grade filters can be installed outdoors but it
is advisable to ensure protection against direct
sunlight.
• Refer to
and
lengths of the power cable of the H07RNF motor.
5 System Description
5.1 User interface
The list describes the parts in
.
Num-
ber
Description
1
Button for running the electric pump in
MANUAL mode. Press and hold the but-
ton to run the electric pump.
2
Button for switching between AUTOMAT-
IC and MANUAL mode.
3
Button for accessing the MENU BASE
(MB) parameters in MANUAL mode,
4 and 5 Buttons for:
• Decreasing or increasing the value of a
parameter selected in MANUAL mode.
• Viewing the operating parameters in
AUTOMATIC mode,
6
Button for selecting parameters in AUTO-
MATIC mode. In MANUAL mode, this is
an alarm reset button.
7
Steady green LED, indicating the power is
on and the converter is running.
8
Steady red LED, indicating a fault. The
LED is illuminated when there is an alarm.
9
Steady yellow LED, indicating the pump is
running.
10
Green LED:
• Illuminated and steady in automatic
mode.
• Flashing in manual parameter configu-
ration mode (basic menu, advanced
menu)
11
Type of display:
• Two digit LEDs, models MMW and
MTW
• LCD with 2 lines of 8 characters, mod-
els MMA and MTA
5.1.1 Locking/unlocking the user interface
en - Original instructions
31
Summary of Contents for Lowara ResiBoost MMA Series
Page 197: ...N 254 V 2 5 DC Bus N A9 T MMW MTW MMA MTA 184 V 7 7 1 MMW MTW MMA MTA A 30m EL SP el 197...
Page 200: ...30 mA RCD B 9 9 1 LED el 200...
Page 229: ...15 4 20mA QCL5 Max Min Max Min G WH BN inst m_03 SC BP it en fr de es pt nl pl el tr 229...
Page 234: ...22 INST G_11_B SC 7 6 5 4 3 2 1 13 8 11 12 2 10 11 2 14 15 it en fr de es pt nl pl el tr 234...
Page 235: ...23 INST G_12_B SC 1 2 7 15 14 6 5 4 3 8 9 2 10 11 12 18 13 it en fr de es pt nl pl el tr 235...
Page 236: ...24 INST G_13_B SC 2 1 13 8 11 12 2 10 11 2 14 15 16 11 17 it en fr de es pt nl pl el tr 236...
Page 237: ...25 13 15 14 INST G_14_B SC 8 9 2 1 2 10 11 12 18 17 16 11 it en fr de es pt nl pl el tr 237...
Page 243: ......