Output frequen-
cy
15-50 Hz
Rated input cur-
rent
(Uin-230V)
6,3A
12,6A
11A
18A
Rated output
current
6
(Uout=230V)
6A
12A
6A
10A
Overcurrent
20%, 10 second maximum
Recommended
line protection
7
13A
16A
16A
25A
Consumption in
standby
4W
Type of load
electric motor
Nominal cosφ
(motor)
≥0,60
≥0,75
IP protection
54
Maximum power
cable section
2,5mm
2
Maximum motor
power cable
section
2,5mm
2
Set-point pres-
sure
0,5 to 16 bar (50 to 1600 kPa)
Ambient tem-
perature
0 to 40°C (32 to 104°F)
Ambient humidi-
ty
< 50%, non-condensing
Elevation
8
≤2000m asl
Protection fuse
(inside)
10A
16A
16A
20A
Cooling
Natural
air
Forced
air
Natural
air
Forced
air
Auxiliary power
supply of pres-
sure sensor
15Vdc
Digital input for
float switch con-
tact
24Vdc, 23,9mA
Dimensions and
weight
See
3.4 Pump specifications
Refer to the user and maintenance manual of the
electric pump. It is essential to consider the limita-
tions of use of the converter together with those of
is responsible for checking the limitations of the
electric pump if they are not specified in this manual.
4 Installation
Precautions
WARNING:
• Observe accident prevention regula-
tions in force.
• Use suitable equipment and protec-
tion.
• Always refer to the local and/or na-
tional regulations, legislation, and co-
des in force regarding the selection of
the installation site, plumbing, and
power connections.
4.1 Electrical requirements
• The local regulations in force overrule specified
requirements listed below.
Electrical connection checklist
Check that the following requirements are met:
• The electrical leads are protected from high tem-
perature, vibrations, and collisions.
• The current type and voltage of mains connec-
tion must correspond to the specifications on the
data plate on the pump.
• It is suggested to supply power to the converter
with a dedicated power line and it is provided
with:
• A high-sensitivity differential switch (30 mA)
[residual current device RCD] suitable for
earth fault currents with pulsating content. In-
terrupter must be marked with the following
symbol:
ELCB
(GFCI)
for models MMW, MTW
and
• A mains isolator switch with a contact gap of
at least 3 mm
The electrical control panel checklist
NOTICE:
The electrical panel must be compatible with the da-
ta of the electric pump powered by the converter. In-
appropriate combinations do not guarantee the pro-
tection of the unit.
Check that the following requirements are met:
• The control panel must protect the converter and
the pump against short circuit. A time lag fuse or
a circuit breaker (Type C model is suggested)
can be used to protect the pump.
• The converter must be programmed correctly to
protect the pump from overloading. Refer to
• A time lag fuse which is inside the converter pro-
tects the pump against short circuits. Refer to
.
The motor checklist
Use cable according to rules with 3 leads (2 + earth/
ground) or 4 leads (3 + earth/ground). All cable must
be heat-resistant up to a minimum of +85°C (185°F).
4.2 Mechanical installation
NOTICE:
en - Original instructions
27
Summary of Contents for Lowara ResiBoost MMA Series
Page 197: ...N 254 V 2 5 DC Bus N A9 T MMW MTW MMA MTA 184 V 7 7 1 MMW MTW MMA MTA A 30m EL SP el 197...
Page 200: ...30 mA RCD B 9 9 1 LED el 200...
Page 229: ...15 4 20mA QCL5 Max Min Max Min G WH BN inst m_03 SC BP it en fr de es pt nl pl el tr 229...
Page 234: ...22 INST G_11_B SC 7 6 5 4 3 2 1 13 8 11 12 2 10 11 2 14 15 it en fr de es pt nl pl el tr 234...
Page 235: ...23 INST G_12_B SC 1 2 7 15 14 6 5 4 3 8 9 2 10 11 12 18 13 it en fr de es pt nl pl el tr 235...
Page 236: ...24 INST G_13_B SC 2 1 13 8 11 12 2 10 11 2 14 15 16 11 17 it en fr de es pt nl pl el tr 236...
Page 237: ...25 13 15 14 INST G_14_B SC 8 9 2 1 2 10 11 12 18 17 16 11 it en fr de es pt nl pl el tr 237...
Page 243: ......