63
0106
0106 PUMP ADDR.
* 1 *
Select desired address for the MASTER Inverter
Possible settings:
1-8
Set desired address on each MASTER Inverter and press
►
button for approx. 3 sec. and
the following massages will appear:
Addressing
Addressing
->
1220 PUMP ADDR.
* 1 *
or
1220 PUMP ADDR.
- 1 -
Addressing done
Addressing failed - retry
When using MASTER and BASIC Inverters together in a multi-pump-system you have to
consider that the BASIC Inverters have their separate address. Otherwise a correct function
of the system couldn’t be guaranteed.
For detailed Information see chapter 9.4.3.2 Addressing.
0110
0110 SET PASSW.
0066
Set Password by pressing
▲
or
▼
Possible settings:
0000 - 9999
The pre-set password (0066) can be changed.
After the password has been changed, it is recommended to note the new password
somewhere.
0115
0115 LOCK FUNCT.
OFF
Possible settings with
▲
or
▼
Possible settings:
ON - OFF
OFF: All parameters in the main menu can be changed without the need of a password.
ON: If the LOCK FUNCTION is activated, no changes can be done in all the parameters.
However the HYDROVAR can be started or stopped by using the push buttons (
▲
or
▼
)
.
In order to change the set value, the LOCK FUNCTION must be set to OFF.
0120
0120 DISP. CONTR.
75 %
Display Contrast
Possible settings:
10 – 100%
Can be adjusted between 10 - 100%, for improved appearance
of the display.
0125
0125 DISP. BRIGHT
100 %
Display Brightness
Possible settings:
10 – 100%
The backlight intensity of the display can be adjusted.