67
0215
0215 RAMP 1
4 sec
Ramp 1: Fast acceleration time
Possible settings:
1 – 250 (1000) sec
•
Excessively fast running up time may cause an error (OVERLOAD) during the HYDROVAR
starts up.
•
Excessively slow running up time may cause a drop of the outgoing pressure during
operation.
0220
0220 RAMP 2
4 sec
Ramp 2: Fast deceleration time
Possible settings:
1 – 250 (1000) sec
•
Excessively fast running down time tends to cause an error (OVERVOLTAGE).
•
Excessively slow running down time tends to generate over pressure.
0225
0225 RAMP 3
70 sec
Ramp 3: Slow acceleration time
Possible settings:
1 – 1000 sec
•
Excessively fast running up time may lead to oscillation and/or an error (OVERLOAD).
•
Excessively slow running up time can cause a drop of the outgoing pressure during
variation of the demand.
0230
0230 RAMP 4
70 sec
Ramp 4: Slow deceleration time
Possible settings:
1 – 1000 sec
•
Excessively fast running down time leads to oscillation of the HYDROVAR and thereby of
the pump.
•
Excessively slow running down time can cause pressure fluctuations during variation of
the demand.
0235
0235 RAMP FMIN A
2.0 sec
Ramp F
min
acceleration
Possible settings:
1.0 – 25.0 sec
Fast running up time to start up the HYDROVAR till the selected MIN. FREQUENCY [0250] is
reached.
Beyond the minimum frequency, RAMP1 [0215] (fast acceleration ramp) starts to work.
•
Excessively fast running up time may cause an error (OVERLOAD) during the HYDROVAR
starts up.