57
Mode CASCADE RELAY:
Device enabled
by
1 MASTER
Inverter
2
fixed speed pump
Relay 1 X10 /1
3
fixed speed pump
Relay 2 X10 /2
4
fixed speed pump
Relay 3 X10 /3
5
fixed speed pump
Relay 4 X10 /4
6
fixed speed pump
Relay 5 X10 /5
7 not
used
8 not
used
23
23 STATUS DEVICE
Stopped
Status of the selected device
Possible messages: Running, Stopped, Disabled, OFF, Preparing (Mode Casc. Serial/Synchr)
relay on, relay off
(Mode: Cascade Relay)
Solorun, Faulted (all Modes)
Shows the status of the device
Mode CASCADE RELAY:
relay_on
->
Relay contact is closed -> fixed-speed-pump is running
relay_off
->
Relay contact is opened -> fixed-speed-pump is stopped
Mode CASCADE SERIAL/SYNCHRON:
running
->
Pump is running
stopped
->
Pump is stopped, because there is no request
disabled
->
Pump is stopped manually
(Stopped with buttons or disabled with parameter ENABLE DEVICE [24])
or by external device (external on/off contact open)
OFF
->
Pump is not connected to power supply
Pump is not connected via RS485 interface
preparing
->
A new unit is connected to the multi-pump system and
Data
is
transferred
solo run
->
Solorun is activated (X1/SL closed)
faulted
->
A failure occurred on the current unit
24
24 ENABLE DEVICE
Enable
Enable – Disable of the selected device
Possible settings:
Enable - Disable
The selected device can be enabled or disabled manually.
(Either in cascade relay / serial / synchron or controller mode).
S
S
G
G