64
0200
0200 SUBMENU CONF
INVERTER
0202
0202 SOFTWARE
HV V01.4
Software version of the control board
If a Remote Display is connected also its software version is shown in this window.
0202
0202 SW RD V01.0
HV V01.4
Software version of the Remote display (RD) and the
control board (HV)
0203
0203 SET VER.INV
sel:00 act:00
Selection of the SW version on the power board
Possible settings:
00 - 02
Manual selection of the required (sel.) and indication of the active (act.) software version
on the power board.
All available versions can be selected if version of BASIC is production date > 05/2008.
After pressing
►
button for 5 seconds the selected specification is activated and DONE is
displayed.
Following parameters [0285], [0286], [0290] and [0291] are added to the menu
(only on
units 5.5-22kW!)
The required version can only be activated if all devices are updated to the new version;
else version will be automatically re set to the next lower version.
Setting 00: all units with production date prior 05/2008
Setting 01: BASIC 1.5-4kW (starting with control board software V01.3 see [47]
Setting 02: BASIC 5.5-22kW (starting with control board software V01.3
0205
0205 MAX. UNITS
06
Maximum number of units
Possible settings:
1 - 8
Select: The maximum number of units which can operate at the same time.
For example:
Cascade Serial:
1 MASTER - and 2 BASIC Inverters are installed in a multi-pump-system
Æ
reasonable values = 1…3
Cascade Relay:
1 MASTER Inverter and 3 fixed speed pumps -> reasonable values = 2…4
S
G
G