Parameter number
Parameter name
Unit of measurement
Description
P60
Multipump – Enable
Speed [P27-P26]
G
rpmx10
This parameter sets the
speed that a pump must
reach before starting the
next assist pump, after a
system pressure drop
below the difference
between P02 and P59.
Default: depending on
the type of pump.
P61
Multipump Synchronous
– Speed Limit [P27-P26]
G
rpmx10
This parameter sets the
speed limit below which
the first assist pump
stops.
Default: depending on
the type of pump.
P62
Multipump Synchronous
– Window [0-100]
G
rpmx10
This parameter sets the
speed limit for the stop of
the next assist pump.
Default: 150 rpmx10.
P63
Multipump – Priority
This parameter shows
the pump priority value
within the multi-pump
set.
This parameter displays
the following information:
Pr1 (Pr1) .. Pr3 (Pr3) or
Pr0 (Pr0)
where:
• Pr1 .. PR3, indicate
that the pump is
communicating with
other pumps of the
displayed priority
order.
• Pr0 indicates that the
pump does not detect
the communication
with other pumps and
is considered alone in
the multi-pump bus
P64
Multipump – Revision
This parameter shows
the multi-pump protocol
revision value used.
6.6.7 Test run configuration
Test Run is a function that starts the pump after the last stop, in order to prevent it from
blocking.
Parameter number
Parameter name
Unit of measurement
Description
P65
Test Run – Time Start
[0-100]
G
h
This parameter sets the
time after which, once
the pump has stopped
for the last time, the Test
Run will start.
Default: 100 h.
6 System Setup and Operation
40
Smart Pump Range INSTRUCTION MANUAL