Item
Terminals
Ref.
Description
Notes
Analog input
0-10V
P2IN/S+
7
Actuator mode 0-10
V input
0–10 VDC
P2C/S-
8
GND for 0-10 V
input
GND, electronic
ground (for S+)
External pressure
sensor [also
Differential]
P1+
9
Power supply
external sensor
+15 VDC
15 VDC, Ʃ max.
100 mA
P1-
10
External sensor
4-20 mA input
4-20 mA
External Start/Stop
START
11
External ON/OFF
input reference
Default short
circuited Pump is
enabled to RUN
STOP
12
External ON/OFF
input
External Lack of
Water
LOW+
13
Low water input
Default short
circuited
Lack of water
detection: enabled
LOW-
14
Low water
reference
Communication bus
B1
15
RS–485 port 1: RS–
485-1N B (-)
ACT, HCS control
mode: RS–485
port1 for external
communication
MSE, MSY control
mode: RS–485 port
1 for multi-pump
systems
A1
16
RS–485 port 1: RS–
485-1P A (+)
GND
17
Electronic GND
Communication bus
B2
18
RS–485 port 2: RS–
485 port 2: RS–
485-2N B (-) active
only with optional
module
RS–485 port2 for
external
communication
A2
19
RS–485 port 2: RS–
485 port 2: RS–
485-2P A (+) active
only with optional
module
GND
20
Electronic GND
Table 8: 3~ I/O terminals
Item
Terminals
Ref.
Description
Notes
Fault signal
C
25
COM - error status
relay
In case of power
cables: use the
M20 cable gland
NO
24
NO - error status
relay
Motor running
signal
C
23
Common contact
In case of power
cables: use the
M20 cable gland
NO
22
Normally open
contact
Auxiliary voltage
supply
15 V
21
Auxiliary voltage
15 VDC
15 VDC, Ʃ max.
100 mA
Analog input
0-10V
S+
20
Actuator mode 0–
10 V input
0–10 VDC
S-
19
GND for 0-10 V
input
GND, electronic
ground (for S+)
4 Installation
22
Smart Pump Range INSTRUCTION MANUAL