Parameter
number
Parameter name
Unit of measurement
Description
P27
Min RPM set
[Min*-ACT set]
G
rpmx10
Minimum pump speed setup.
P28
Ramp 1 [1–250]
G
s
This parameter adjusts the fast acceleration time.
It affects the control of the pump for HCS, MSE and
MSY control modes (also see Par. 6.6.2).
Default: 3 s.
P29
Ramp 2 [1–250]
G
s
This parameter adjusts the fast deceleration time
It affects the control of the pump for HCS, MSE and
MSY control modes (also see Par. 6.6.2).
Default: 3 s.
P30
Ramp 3 [1–999]
G
s
This parameter adjusts the slow acceleration.
It determines:
• The Hydrovar
®
adjustment speed, in case of small
flow rate variations
• The constant outgoing pressure.
The ramp depends on the system being controlled,
and affects the control of the pump in HCS, MSE and
MSY modes (also see Par. 6.6.2).
Default: 35 s.
P31
Ramp 4 [1–999]
G
s
Adjustment of the slow deceleration time (also see
Par. 6.6.2).
Other characteristics: as for Ramp 3.
P32
Ramp Speed Min
Acceleration [2.0-25.0]
G
s
This parameter sets the fast acceleration time.
It represents the acceleration ramp used by the
Hydrovar
®
controller until the minimum speed of the
pump is reached (P27).
It affects the control of the pump for HCS, MSE and
MSY control modes (also see Par. 6.6.2).
Default: 2.0 s.
P33
Ramp Speed Min
Deceleration [2.0-25.0]
G
s
This parameter sets the fast deceleration time.
It represents the deceleration ramp used by the
Hydrovar
®
controller for stopping the pump once the
minimum speed of the pump is reached (P27).
It affects the control of the pump for HCS, MSE and
MSY control modes (also see Par. 6.6.2).
Default: 2.0 s.
6 System Setup and Operation
Smart Pump Range INSTRUCTION MANUAL
35