Parameter
number
Parameter name
Unit of measurement
Description
P48
Lack Of Water Switch Input
[DIS, ALR, ERR]
This parameter enables/disables the management of
the lack of water input (see Par. 4.3.3, terminals 13
and 14).
It defines the behaviour of the unit when the lack of
water input is enabled and the switch is open:
• DIS (DIS): the unit doesn’t manage the information
coming from the "lack of water" input.
• ALr (ALr): the unit reads the "lack of water" Input
(enabled) and reacts, at the opening of the switch,
by displaying the corresponding alarm A06 on the
display, and keeping the motor running.
• Err (Err): Err, the unit reads the Lack Of Water
Input (enabled) and reacts, at the opening of the
switch, by stopping the motor and generating the
corresponding error E11. The error condition is
removed when the switch closes again and the
motor is started.
Default: ERR.
6.6.5 RS–485 Interface parameters
Parameter name
Parameter number
Unit of measurement
Description
P50
Communication protocol
[MOD, BAC]
This parameter selects
the specific protocol on
the communication port:
• NOD (MOD): Modbus
RTU
• BAC (BAC): BACnet
MS/TP.
Default: MOD.
P51
Communication protocol
- Address [1-247]/[0-127]
This parameter sets the
desired address for the
unit, when connected to
an external device,
depending on the
protocol selected in P50:
• MOD: any value in the
1-247 range
• BAC: any value in the
0-127 range.
P52
Comm Protocol –
BAUDRATE [4.8, 9.6,
14.4, 19.2, 38.4, 56.0,
57.6 KBPS]
kbps
This parameter sets the
desired baud rate for the
communication port.
Default: 9.6 kbps.
P53
BACnet Device ID Offset
[0-999]
This parameter sets the
hundreds, tens and units
of the BACnet Device ID.
Default: 002.
Device ID default:
84002.
P54
Comm Protocol –
Configuration [8N1, 8N2,
8E1, 8o1]
This parameter sets the
length of the data bits,
the parity and the length
of the STOP bits.
6 System Setup and Operation
38
Smart Pump Range INSTRUCTION MANUAL