Studer Innotec SA
Xtender
User manual
V4.6.0
50
Access
level
Param.
N°
Denomination / description
Fact. value
2
Mod.
value
Inst.
1331 Start hour (AUX 2)
07:00 hh:mm
Inst.
1332 End hour (AUX 2)
20:00 hh:mm
Expert
1333 Xtender is OFF (AUX 2)
Yes
Expert
1334 Battery undervoltage alarm (AUX 2)
Yes
Expert
1335 Battery overvoltage (AUX 2)
Yes
Expert
1336 Inverter or Smart-Boost overload (AUX 2)
Yes
Expert
1337 Overtemperature (AUX 2)
Yes
Expert
1339 Active charger (AUX 2)
No
Expert
1340 Active inverter (AUX 2)
No
Expert
1341 Active Smart-Boost (AUX 2)
No
Expert
1342 AC input presence but with fault (AUX 2)
No
Expert
1343 AC input presence (AUX 2)
No
Expert
1344 Transfer contact ON (AUX 2)
No
Expert
1345 AC out presence (AUX 2)
No
Expert
1346 Bulk charge phase (AUX 2)
No
Expert
1347 Absorption phase (AUX 2)
No
Expert
1348 Equalization phase (AUX 2)
No
Expert
1350 Floating (AUX 2)
No
Expert
1351 Reduced floating (AUX 2)
No
Expert
1352 Periodic absorption (AUX 2)
No
Expert
1354 Use dynamic compensation of battery level (AUX 2)
No
Expert
1355 Battery voltage 1 activate (AUX 2)
No
Expert
1356 Battery voltage 1 (AUX 2)
12/24/48 Vdc
Expert
1357 Delay 1 (AUX 2)
5 min
Expert
1358 Battery voltage 2 activate (AUX 2)
No
Expert
1359 Battery voltage 2 (AUX 2)
11.5/23/46.1 Vdc
Expert
1360 Delay 2 (AUX 2)
5 min
Expert
1361 Battery voltage 3 activate (AUX 2)
No
Expert
1362 Battery voltage 3 (AUX 2)
11/22.1/44.2 Vdc
Expert
1363 Delay 3 (AUX 2)
5 min
Expert
1364 Battery voltage to deactivate (AUX 2)
12.6/25.2/50.4 Vdc
Expert
1365 Delay to deactivate (AUX 2)
5 min
Expert
1367 Inverter power level 1 activate (AUX 2)
No
Expert
1368 Power level 1 (AUX 2)
120 % Pnom
Expert
1369 Time delay 1 (AUX 2)
0 min
Expert
1370 Inverter power level 2 activate (AUX 2)
No
Expert
1371 Power level 2 (AUX 2)
80 % Pnom
Expert
1372 Time delay 2 (AUX 2)
5 min
Expert
1373 Inverter power level 3 activate (AUX 2)
No
Expert
1374 Power level 3 (AUX 2)
50 % Pnom
Expert
1375 Time delay 3 (AUX 2)
30 min
Expert
1376 Inverter power level to deactivate (AUX 2)
40 % Pnom
Expert
1377 Time delay to deactivate (AUX 2)
5 min
Expert
1380 Day of the week (AUX 2)
None days
Expert
1381 Start hour (AUX 2)
07:00 hh:mm
Expert
1382 End hour (AUX 2)
20:00 hh:mm
Expert
1384 Day of the week (AUX 2)
None days
Expert
1385 Start hour (AUX 2)
07:00 hh:mm
Expert
1386 End hour (AUX 2)
20:00 hh:mm
Expert
1388 Day of the week (AUX 2)
None days
Expert
1389 Start hour (AUX 2)
07:00 hh:mm
Expert
1390 End hour (AUX 2)
20:00 hh:mm
Basic
1395 Restore default settings
-
Inst.
1399 OFF of the Xtenders
-
Expert
1404 Time period for batteries undervoltages counting
0 sec